ASFIFF12 High Speed
vacon • 63
24-hour s358 (0)40 837 1150 • Email: [email protected]
3
Fault
code
Fault
Possible cause
Correcting measures
communication
fault
keypad or NCDrive and the frequency
converter is broken.
keypad cable.
53
Fieldbus fault
The data connection between the
fieldbus Master and the fieldbus board
is broken
Check installation.
If installation is correct contact the
nearest Vacon distributor.
54
Slot fault
Defective option board or slot
Check board and slot.
Contact the nearest Vacon distributor.
56
PT100 board
temp. fault
Temperature limit values set for the
PT100 board parameters have been
exceeded
Find the cause of temperature rise
57
Identification
(Warning only)
Identification run have been failed
- Run command was removed before
identification was ready
- Motor is not connected to frequency
converter.
- There is load on motor shaft.
58
Brake
Actual status of the brake is opposite
than control signal.
Check mechanical brake condition and
connections.
59
Follower
Communication
SystemBus or CAN communication is
broken between master and follower
Check parameters from expanderboard
and optical fibre or CAN cable.
60
Cooling
Liquid cooled drive cooling circulation
have been failed
Check reason for cooling failure from
external system.
61
Speed Error
Motor speed is not the same than
reference.
-Check encoder connegtion
- PMS motor has been gone over pull
out torque.
62
Run Disable
- Run Enable signal is Low
- Check reason for Run Enable signal.
63
Emergency
stop (Warning
only)
Digital input or fieldbus have give
command to make emergency stop
New run command is accepted after
emergency stop is reset.
64
Input switch
open
Drive input switch is opened
Check the main power switch of the
drive.
72
Trial Time
Application is used without licence key.
You have given too high frequency
value as maximum frequency.
Contact Vacon factory to get licence key.
Use application below 1700 Hz
Table 7-1. Fault codes