Parameters
vacon • 80
Service support: find your nearest Vacon service center at www.vacon.com
6
P3.5.1.15
DigIN Slot0.2
407
Must be on to set drive in Ready state
P3.5.1.16
DigIN Slot0.2
1041
Drive may be ready but start is blocked as long
as interlock is on (Damper interlock).
P3.5.1.17
DigIN Slot0.2
1042 As above.
P3.5.1.21
DigIN SlotA.4
419
Binary selector for Preset speeds (0-7). See
page 76.
P3.5.1.22
DigIN SlotA.5
420
Binary selector for Preset speeds (0-7). See
page 76.
P3.5.1.23
DigIN Slot0.1
421
Binary selector for Preset speeds (0-7). See
page 76.
P3.5.1.24
MotPot UP
DigIN Slot0.1
418
FALSE = Not active
TRUE = Active (Motor potentiometer reference
INCREASES until the contact is opened)
P3.5.1.25
MotPot DOWN
DigIN Slot0.1
417
FALSE = Not active
TRUE = Active (Motor potentiometer reference
DECREASES until the contact is opened)
P3.5.1.27
Timer 1
DigIN Slot0.1
447
Rising edge starts Timer 1 programmed in
Group 3.12: Timer functions parameter group
P3.5.1.28
Timer 2
DigIN Slot0.1
448
See above
P3.5.1.29
Timer 3
DigIN Slot0.1
449
See above
P3.5.1.30
PID SP Boost
DigIN Slot0.1
1046
FALSE = No boost
TRUE = Boost
P3.5.1.31
PID SP Selection
DigIN Slot0.1
1047
FALSE = Setpoint 1
TRUE = Setpoint 2
P3.5.1.32
ExtPID StartSignal
DigIN Slot0.2
1049
FALSE = PID2 in stop mode
TRUE = PID2 regulating
This parameter will have no effect if the exter-
nal PID-controller is not enabled in Group 3.14:
ExtPID Controller.
P3.5.1.33
ExtPID SP Select
DigIN Slot0.1
1048
FALSE = Setpoint 1
TRUE = Setpoint 2
P3.5.1.40
MainCounter1Reset
DigIN Slot0.1
490
Reset the counter from digital input.
TRUE = Reset
P3.5.1.48
AutoClean Activ.
DigIN Slot0.1
1715
Start the Auto-cleaning sequence.
The sequence will be aborted if activation sig-
nal is removed before the sequence has been
completed.
NOTE!
The drive will start if the input is acti-
vated!
P3.5.1.49
Param. Set 1/2 Sel.
DigIN Slot0.1
496
Parameter set 1/2 selection.
Open= Parameter Set 1
Closed= Parameter Set 2
P3.5.1.50
User Defined Fault 1
DigIN Slot0.1
1552
3
Digital input selection for activating User
Defined Fault (1 or 2).
Open= No operation
Closed= Fault Activated
P3.5.1.51
User Defined Fault 2
DigIN Slot0.1
1552
4
Digital input selection for activating User
Defined Fault (1 or 2).
Open= No operation
Closed= Fault Activated
P3.5.1.52
Energy Counter reset
DigIN Slot0.1
1933 Energy Counter reset
P3.5.1.53
Mains supply on
DigIN Slot0.1
1934 Mains supply on
Table 59. Digital input settings
Code
Parameter
Default
ID
Description
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......