vacon • 129
Parameters
6
6.2.8
Flux Braking
Instead of DC braking, flux braking is a useful way to raise the braking capacity in cases where
additional brake resistors are not needed.
When braking is needed, the frequency is reduced and the flux in the motor is increased, which
in turn increases the motor's capability to brake. Unlike DC braking, the motor speed remains
controlled during braking.
The flux braking can be set ON or OFF.
NOTE
: Flux braking converts the energy into heat at the motor, and should be used intermit-
tently to avoid motor damage.
6.2.9
Digital inputs
Contact open:
Start of motor
disabled
Contact closed: Start of motor
enabled
The AC drive is stopped according to the selected function at P3.2.5. The follower drive will al-
ways coast to stop.
The drive cannot be started if any of the interlocks are open.
The function could be used for a damper interlock, preventing the drive to start with damper
closed.
P3.5.1.52
E
NERGY
COUNTER
RESET
This parameter enables reset of Energy counter.
P3.5.1.53
M
AINS
SUPPLY
ON
In case the drive is fed by mains supply, the controller knows this situation through a specific
digital input.
The functions related to DC voltage (start enable, MPPT) are disabled in this condition.
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......