Parameters
vacon • 120
Service support: find your nearest Vacon service center at www.vacon.com
6
P3.1.4.12.2 I/
F
START
FREQ
I/f start function is used when the drive’s output frequency is below this frequency limit. When
the output frequency exceeds this limit, the drive operation mode is changed back to normal
U/f control mode.
This parameter defines the current to be fed to the motor when the I/f start function is activat-
ed.
6.2.3
Start/Stop Setup
Table 113.
Selection
number
Selection name
Description
0
Coasting
The motor is allowed to stop on its own inertia. The control by the
drive is discontinued and the drive current drops to zero as soon as
the stop command is given.
1
Ramp to min
frequency
After the Stop command, the speed of the motor is decelerated to
minimum frequency according to the set deceleration parameters .
2
Ramp to zero
frequency
After the Stop command, the speed of the motor is decelerated to
zero frequency according to the set deceleration parameters .