vacon • 69
Parameters
6
6.1.2.3
Group 3.1.3: Limits
6.1.2.4
Group 3.1.4: Open loop
P3.1.2.11
Under Volt. Control
0
1
1
608
0 = Disabled
1 = Enabled
P3.1.2.12
Energy optimization
0
1
0
666
The drive searches for the
minimum motor current in
order to save energy and to
lower the motor noise. This
function can be used e.g. in
fan and pump applications
0 = Disabled
1 = Enabled
P3.1.2.13
StatorVoltAdjust
50.0
150.0
%
100.0
659
Parameter for adjusting the
stator voltage in permanent
magnet motors.
P3.1.2.14
Overmodulation
0
1
1
Maximizes drive output volt-
age, but increases motor
current harmonics.
0= Disabled
1= Enabled
Table 47. Motor limit settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.1.3.1
Current limit
Varies
Varies
A
Varies
107
Maximum motor current
from AC drive
P3.1.3.2
MotorTorqueLimit
0.0
300.0
%
300.0
1287
Maximum motoring side
torque limit
P3.1.3.3
GenerTorqueLimit
0.0
300.0
%
300.0
1288
Maximum generating side
torque limit
P3.1.3.4
MotorPowerLimit
0.0
300.0
%
300.0
1290
Maximum motoring side
power limit
P3.1.3.5
GenerPowerLimit
0.0
300.0
%
300.0
1289
Maximum generating side
power limit
Table 48. Open loop settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.1.4.1
0
2
0
108
Type of U/f curve between
zero frequency and the field
weakening point.
0=Linear
1=Squared
2=Programmable
P3.1.4.2
Field WeakngPnt
8.00
Hz
Varies
602
The field weakening point is
the output frequency at
which the output voltage
reaches the field weakening
point voltage
Table 46. Motor control
Code
Parameter
Min
Max
Unit
Default
ID
Description
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......