Startup
P1.34.7
SP 1 Sleep Freq
0.00
320.00
Hz
0.00
1016
Drive goes to sleep mode
when the output frequency
stays below this limit for a
time greater than that
defined by parameter
Sleep
delay
.
P1.34.8
SP 1 Sleep Delay
0
3000
s
0
1017
The minimum amount of
time the frequency has to
remain below the Sleep level
before the drive is stopped.
P1.34.9
SP 1 WakeUpLevel
Varies
0.00
1018
Defines the level for the PID
feedback value wake-up
supervision. Uses selected
process units.
P1.34.10
Preset Freq 1
P1.3
P1.4
Hz
10.0
105
Preset Freq 1
Table 5. PID Control start-up wizard menu