vacon • 163
Fault
33
320
Fire mode
enabled
Fire mode of the drive is enabled. The
drive's protections are not in use.
Check the parameter settings
37
360
Device changed
(same type)
Option board changed for one previ-
ously inserted in the same slot. The
board’s parameter settings are saved.
Device is ready for use. Old
parameter settings will be
used.
38
370
Device changed
(same type)
Option board added. The option board
was previously inserted in the same
slot. The board’s parameter settings
are saved.
Device is ready for use. Old
parameter settings will be
used.
39
380
Device removed
Option board removed from slot.
Device no longer available.
40
390
Device unknown
Unknown device connected (power
unit/option board)
Device no longer available.
41
400
IGBT tempera-
ture
IGBT temperature (unit tempe
I
2
T) is too high.
Check loading.
Check motor size.
Make identification run.
44
430
Device changed
(different type)
Option board changed or Power unit
changed. No parameter settings are
saved.
Set the option board parame-
ters again if option board was
changed. Set converter param-
eters again if power unit was
changed.
45
440
Device changed
(different type)
Option board added. The option board
was not previously present in the same
slot. No parameter settings are saved.
Set the option board parame-
ters again.
46
662
Real Time Clock
RTC battery voltage level is low and the
battery should be changed.
Replace the battery.
47
663
Software updated
Software of the drive has been updated
(either the whole software package or
application).
No actions needed.
50
1050
AI low fault
At least one of the available analogue
input signals has gone below 50% of
the defined minimum signal range.
Control cable is broken or loose.
Signal source has failed.
Change the failed parts.
Check the analog input circuit.
Check that parameter
AI1 sig-
nal range
is set correctly.
51
1051
External Fault
Fault activated by digital input.
Check the digital input or the
device connected to it.
Check the parameter settings.
52
1052
1352
Keypad commu-
nication fault
The connection between the control
keypad and frequency converter is bro-
ken
Check keypad connection and
possible keypad cable
53
1053
Fieldbus commu-
nication fault
The data connection between the field-
bus master and fieldbus board is bro-
ken
Check installation and fieldbus
master.
54
1654
Slot D fault
Defective option board or slot
Check board and slot.
1754
Slot E fault
Fault
code
Fault
ID
Fault name
Possible cause
Remedy
Table 125. Fault codes and descriptions.
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......