3
vacon • 11
Startup
P1.22
I/O A Ref sel
1
9
5
117
Selection of ref source when
control place is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
P1.23
Keypad Ref sel
1
9
2
121
Selection of ref source when
control place is keypad:
See P1.22
P1.24
Fieldbus Ref sel
1
9
3
122
Selection of ref source when
control place is Fieldbus:
See P1.22
P1.25
AI1 signal range
0
1
0
379
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
P1.26
AI2 signal range
0
1
1
390
0 = 0…10V / 0…20mA
1 = 2…10V / 4…20mA
Table 1. Quick setup parameter group
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......