vacon • 91
Parameters
6
6.1.10.5
Group 3.9.6: Temperature input fault 1
NOTE!
This parameter group is visible only with an option board for temperature measure-
ment (OPT-BH) installed.
Table 76. Temperature input fault 1 settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.9.6.1
Temperature signal 1
0
63
0
739
Selection of signals to use for
alarm and fault triggering.
B0 = Temperature Signal 1
B1 = Temperature Signal 2
B2 = Temperature Signal 3
B3 = Temperature Signal 4
B4 = Temperature Signal 5
B5 = Temperature Signal 6
Max value is taken of the
chosen signals and used for
alarm/fault triggering.
NOTE!
Only 6 first tempera-
ture inputs are supported
(counting boards from slot A
to slot E).
P3.9.6.2
Alarm limit 1
-30.0
200.0
°C
120.0
741
Temperature limit for trig-
ging alarm.
NOTE!
Only
inputs chosen with parame-
ter P3.9.6.1 are compared.
P3.9.6.3
Fault limit 1
-30.0
200.0
°C
120.0
742
Temperature limit for trig-
ging alarm.
NOTE!
Only
inputs chosen with parame-
ter P3.9.6.1 are compared.
P3.9.6.4
Fault limit response 1
0
3
2
740
0 = No response
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......