Startup
vacon • 14
Service support: find your nearest Vacon service center at www.vacon.com
3
3.2.1
Standard application
You can use the Standard application in speed-controlled processes where no special func-
tions are necessary, for example pumps, fans, or conveyors.
It is possible to control the drive from the keypad, Fieldbus or I/O terminal.
When you control the drive with the I/O terminal, the frequency reference signal is connected
to AI1 (0…10V) or AI2 (4…20mA). The connection depends the type of the signal. There are also
3 preset frequency references available. You can activate the preset frequency references with
DI4 and DI5. The start/stop signals of the drive are connected to DI1 (start forward) and DI2
(start reverse).
It is possible to configure all the drive outputs freely in all the applications. There are 1 ana-
logue output (Output Frequency) and 3 relay outputs (Run, Fault, Ready) available on the basic
I/O board.
3.2.1.1
M1.31 Standard
Table 2. Standard start-up wizard menu
Code
Parameter
Min
Max
Unit
Default
ID
Description
P1.31.1
Preset Freq 1
P1.3
P1.4
Hz
10.0
105
Make the selection of a
preset frequency with
the digital input DI4.
P1.31.2
Preset Freq 2
P1.3
P1.4
Hz
15.0
106
Make the selection of a
preset frequency with
the digital input DI5.
P1.31.3
Preset Freq 3
P1.3
P1.4
Hz
20.0
126
Make the selection of a
preset frequency with
the digital input DI4
and DI5.
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......