Parameters
vacon • 104
Service support: find your nearest Vacon service center at www.vacon.com
6
6.1.14.6
Group 3.13.6: Feedback Superv.
Process supervision is used to control that the
PID Feedback value
(process actual value)
stays within predefined limits. With this function you can e.g. detect a major pipe burst and stop
unnecessary flooding. See more on page 146.
6.1.14.7
Group 3.13.7: Press.Loss.Comp.
P3.13.5.6
0
3000
s
0
1076
The minimum amount of
time the frequency has to
remain below the Sleep level
before the drive is stopped.
P3.13.5.7
Varies
0.00
1077
Defines the level for the PID
feedback value wake-up
supervision. Uses selected
process units.
P3.13.5.8
SP 2 WakeUpMode
0
1
0
1020
Select if wake up level should
work as an absolute level or
as an offset below the actual
setpoing value.
0 = Absolute Level
1 = Relative Setpoint
Table 96. Process supervision parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.6.1
0
1
0
735
0 = Disabled
1 = Enabled
P3.13.6.2
Varies
Varies
Varies
Varies
736
Upper actual/process value
supervision
P3.13.6.3
Varies
Varies
Varies
Varies
758
Lower actual/process value
supervision
P3.13.6.4
0
30000
s
0
737
If the desired value is not
reached within this time a
fault or alarm is created.
P3.13.6.5
Supervision Fault
0
3
2
749
0 = No action
1 = Alarm
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
Table 97. Pressure loss compensation parameters
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.7.1
0
1
0
1189
Enables pressure loss com-
pensation for setpoint 1.
0 = Disabled
1 = Enabled
P3.13.7.2
SP 1 Max Comp.
Varies
Varies
Varies
Varies
1190
Value added proportionally to
the frequency.
Setpoint compensation = Max
compensation * (FreqOut-
MinFreq)/(MaxFreq-MinFreq)
Table 95. Sleep function settings
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......