Parameters
vacon • 68
Service support: find your nearest Vacon service center at www.vacon.com
6
P3.1.2.3
Switching Freq
1.5
Varies
kHz
Varies
601
Increasing the switching
frequency reduces the
capacity of the AC drive. It is
recommended to use a
lower frequency when the
motor cable is long in order
to minimize capacitive cur-
rents in the cable. Motor
noise can also be minimised
using a high switching fre-
quency.
P3.1.2.4
0
1
0
631
The automatic motor identi-
fication calculates or mea-
sures the motor parameters
that are needed for opti-
mum motor and speed con-
trol.
0 = No action
1 = At standstill
P3.1.2.5
Magnetizing current
0.0
2*IH
A
0.0
612
Motor magnetizing current
(no-load current). The val-
ues of the U/f parameters
are identified by the magne-
tizing current if given before
the identification run. If this
value is set to zero, magne-
tizing current will be inter-
nally calculated.
P3.1.2.6
0
1
0
653
Enabling this function pre-
vents the drive from tripping
when the motor switch is
closed and opened e.g.
using flying start.
0 = Disabled
1 = Enabled
P3.1.2.7
0.00
50.00
%
0.00
620
The drooping function
enables speed drop as a
function of load. Drooping
will be defined in percent of
nominal speed at nominal
load.
P3.1.2.8
Load drooping time
0.00
2.00
s
0.00
656
Load drooping is used in
order to achieve a dynamic
speed drooping because of
changing load. This param-
eter defines the time during
which the speed is restored
to the level it was before the
load increase.
P3.1.2.9
Load drooping mode
0
1
0
1534
0 = Normal; Load drooping
factor is constant through
the whole frequency range
1 = Linear removal; Load
drooping is removed linearly
from nominal frequency to
zero frequency
Table 46. Motor control
Code
Parameter
Min
Max
Unit
Default
ID
Description
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......