vacon • 71
Parameters
6
Figure 21. I/f start
Table 49. I/f start parameters
6.1.2.6
Group 3.1.4.13: Stabilators
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.1.4.12.1
0
1
0
534
0 = Disabled
1 = Enabled
P3.1.4.12.2
0.0
%
15.0
535
Output frequency limit
below which the defined I/f
start current is fed to motor.
P3.1.4.12.3
0.0
100.0
%
80.0
536
The current fed to the motor
when the I/f start function is
activated.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.1.4.13.1
TorqStabGain
0.0
500.0
%
50.0
1412
Gain of the torque stabilator
in open loop motor control
operation.
P3.1.4.13.2
TorqStabGainFWP
0.0
500.0
%
50.0
1414
Gain of the torque stabilator
at field weakening point in
open loop motor control
operation.
P3.1.4.13.3
TorqStabDampTC
0.0005
1.0000
s
0.0050
1413
Damping time of torque sta-
bilizer
P3.1.4.13.4
TorqStabDampTC
PMM
0.0005
1.0000
s
0.0500
1735
Damping time constant of
torque stabilizer for PM-
motor.
Motor Current
Time
[s]
I/
f Start
Frequency
I/
f Start Current
Output Frequency
9240.emf
Содержание 100X series
Страница 1: ...vacon 100 x ac drives Solar pump application manual ...
Страница 2: ......
Страница 6: ...vacon 3 Vacon 100X Solar Pump Application 1 ...
Страница 8: ...2 vacon 5 Safety ...
Страница 59: ...User Interfaces vacon 56 Service support find your nearest Vacon service center at www vacon com 4 ...
Страница 160: ...vacon 157 Parameters 6 ...
Страница 169: ...Fault vacon 166 Service support find your nearest Vacon service center at www vacon com 7 ...
Страница 170: ...7 vacon 167 Fault ...
Страница 171: ......