39
Figure 9-2 - User Interface
9.3
Program Boiler Control
Key
Description
- Manual Lockout Reset
- Enter/Exit user menu
- Go to previous screen
- Select a menu item
- Confirm new parameter value
- Scroll up to next menu item
- Increase value
- Scroll down to next menu item
- Decrease value
Table 12 -
Default Table
Control Parameter
Factory Default
Setting
Setting Range
*Actual
Parameter
Settings
Standard
Metric
Standard
Metric
User
Menu
Settings
Central Heating Setpoint
140°F
60°C
104-195°F
40-91°C
DHW Setpoint
180°F
82°C
104-195°F
40-91°C
Temperature Units
°F
°F/°C
Installer
Menu
Boiler
Configuration
Boiler Address
0
0-15
Low Water Cutoff
Enabled
Enable/Disabled
Pump Mode
0
0 & 4
Service Reminder Status
On
ON/OFF
Service Reminder Days
365 Days
1- 999 Days
CH Settings
CH Mode
1
0, 1, 2, 3
Warm Weather Shutdown
70°F
21°C
35-100°F
2-38°C
Reset Curve Design Temperature - Boiler
180°F
82°C
60-195°F
40-91°C
Reset Curve Design Temperature - Outdoor
25°F
-4°C
-60-32°F
-51-25°C
Reset Curve Mild Weather Temperature - Boiler
100°F
37°C
35-120°F
2-49°C
Reset Curve Mild Weather Temperature - Outdoor
70°F
21°C
35-85°F
2-29°C
Reset Curve Boiler Minimum Temperature
70°F
21°C
40-180°F
4-82°C
Reset Curve Boiler Maximum Temperature
180°
82°C
80-195°F
27-91°C
Boost Function Temperature
0°F
0°C
0-36°F
0-20°C
Boost Function Time
20 Minutes
1-120
Maximum Power CH
100%
1-100%
DHW
Settings
DHW Mode
0
0/2
DHW Maximum Priority Time
30 Minutes
1-60 minutes
Maximum Power DHW
100%
1-100%
Fan Speeds
Minimum Fan Speed
Varies by Model
+1020 / -0
Ignition Fan Speed
Varies by Model
+1020/ -540
* List parameters in event of Control Module Failure to reprogram your settings.
9 - START UP PROCEDURE
Boiler is factory programmed with following factory
default settings, Table 12.
Parameters can be adjusted to suit particular application
using the User Interface. See figure 9-2.
Detailed explanation of each can be found in Appendix A -
Control Module.
List parameters in event of factory default parameters are
changed.
PN 240011320 Rev. G 10/01/2021]