Information and specifications outlined in this manual in effect at the
time of printing of this manual. reserves the right to
discontinue, change specifications or system design at any time without
notice and without incurring any obligation, whatsoever.
2 - INTRODUCTION
2.4
Designated Use
• Hot water heating boiler.
• Indoor installation.
• Closet or alcove installation.
• Direct vent boiler.
•
For use with natural gas or liquefied petroleum gases
(LP/propane).
2.5
The unit MUST NOT:
• Directly heat potable water. Indirect heating is acceptable.
• Heat water with non-hydronic heating system chemicals
present (example, swimming pool water).
• Exceed 150 psig (1.03 MPa) maximum allowable working
pressure.
• Exceed 195°F (90.5°C) system design temperature.
2.6
Operational Features
• Modulating: 20-100%.
• Integral Dual Limit.
•
Integral Low Water Cutoff (with test button).
• Outdoor Temperature Reset.
• Integral Multiple Boiler Control.
• Heat exchanger over heat protection.
2 - INTRODUCTION
2.1
Installation shall conform to requirements of authority
having jurisdiction or in absence of such requirements:
• United States
• National Fuel Gas Code, ANSI Z223.1/NFPA 54.
• National Electrical Code, NFPA 70.
2.2
Where required by authority having jurisdiction,
installation shall conform to Standard for Controls and Safety
Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
Additional manual reset low water cutoff may be required.
2.3 Requirements for Commonwealth of Massachusetts:
Boiler installation must conform to Commonwealth of
Massachusetts code 248 CMR which includes but is not limited
to:
Installation by licensed plumber or gas fitter.
PN 240011320 Rev. G 10/01/2021]