7.1
General
• Use piping materials and joining methods acceptable
to authority having jurisdiction. In absence of such
requirements:
• USA - National Fuel Gas Code, ANSI Z223.1/NFPA 54
•
Size and install gas piping system to provide sufficient gas
supply to meet maximum input at not less than minimum
supply pressure. See Table 10.
• Support piping with hooks straps, bands, brackets,
hangers, or building structure components to prevent or
dampen excessive vibrations and prevent strain on gas
connection. Boiler will not support piping weight.
• Use thread (joint) compound (pipe dope) suitable for
liquefied petroleum gas.
• Provide sediment trap up stream of gas valve.
•
Install manual main shutoff valve outside of jacket. See
figure 7-2.
7.2
Conversion Kit Instructions
• See Gas Conversion Kit Instructions included with Boiler.
Table 10 -
Gas Supply Pressure
CAUTION
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow gas supplier’s
instructions.
•
If you cannot reach your gas supplier, call the fire
department.
!
!
Gas Supply Pressure
MODEL
Natural Gas
Propane
Min.
Max.
Min.
Max.
050
3.0" w.c.
(0.7 kPa)
13.5" w.c.
(3.3 kPa)
5.0" w.c.
(1.2 kPa)
13.5" w.c.
(3.4 kPa)
075
100
150
200
299
FIGURE 7-1 Gas Connection
Note:
See Glossary - Piping Table 16
Gas Connection
7 - GAS SUPPLY PIPING
Note
Use two (2) wrenches when tightening and fitting
to pipe boiler's threaded fittings. Boiler's internal
piping can be damaged if subjected to excessive
torque.
PN 240011320 Rev. G 10/01/2021]