13 - TROUBLE SHOOTING
Screen Display
Explanation
Go to Page For
Troubleshooting
Low water cutoff sees no water.
Go to Page 59
Flue temperature sensor sees temperature
higher than 200°F.
Go to Page 60
Return water temperature sensor sees
temperature higher than 200°F.
Go to Page 61
Control board internal error. Power down then
power up boiler. If error repeatedly occurs
replace control module.
Replace Control
Module
Boiler is powered by three wires, hot, neutral
and ground. E44 displays when neutral wire is
not neutral.
Go to Page 61
Control board sees power supply frequency not
in range of 59 to 61 Hz.
Go to Page 62
Boiler power supply ground wire is not
grounded.
Go to Page 63
Control board internal error. Power down then
power up boiler. If error repeatedly occurs
replace control module.
Replace Control
Module
Supply temperature sensor is open. No
continuity.
Go to Page 63
Return water temperature sensor is open. No
continuity.
Go to Page 64
Flue temperature sensor is open. No continuity.
Note: If "L" indicator appears Flue Sensor is
open.
Go to Page 65
Supply water temperature sensor is shorted.
'0' Ohm
Go to Page 65
Return water temperature sensor is shorted. '0'
Ohm
Go to Page 66
Flue temperature sensor is shorted. '0' Ohm
Go to Page 66
Reset button was pressed too many times.
Error Clears in 1-2
minutes
Fault detected in blower motor system.
Go to page 62
Blocking Error
F l u e G a s E r r o r
E 39
L
PN 240011320 Rev. G 10/01/2021]