54
-
Lo-ck�ut
Alarm
A
O
1
lgnit
error
In
st
al
l
Enter
the
Installer
Menu
and
place
the
boiler
int
o
test
mode
in
high
fire.
Once
the
boiler
sta
rt
s,
go
to
the
boiler
status
screen
and
monitor
the
flame
signal.
Is
the
flame
signal
greater
than
7.0uA
w
he
n
running
on
hi
h
fire?
YES
Has gas valve been adjusted
per
instructions?
YES
C
h
ec
k
ven
t
termination
for
proper
consideration
of
wind
ef
fe
ct
s
Is
this
boiler
to
run
with
propane
gas?
Is
this
a
new
boiler
on
firs
t
startup?
YES
Is
the
Gas
Shutoff
Va
lv
e
closed?
YES
Open
gas
shutoff
valves
Reset
the
boiler
by
Check
all
wires
including
the
ig
ni
ter
and
flame
sens
or
leads.
Check
for
proper
and
tight
connections
to
control
board.
Are
all
wires
connected?
YES
Ins
pec
t Vent
System
fo
r
bl
oc
kag
es
.
Is
the
vent
sy
st
em
cl
ea
r?
YES
Does
the
bo
iler
ignite
and
stay
running?
pressing
the
'Reset'
button.
When
the
boiler
tries
to
ignite,
is
there
a
strong,
consistent
spark
ev
id
en
t
throught
the
sight
glass?
Disconnect
the
gas
valve
electrical
harness
and
close
the
gas
shutoff
valve.
YES
YES
Remove
the
flame
14---
---
sens
or
and
igniter
and
inspect.
Is
there
any
indication
of
da
m
ag
e
or
debris
baked
on?
YES
Replace/clean
flame
sensor
or
igniter
With
the
ign
iti
on
lead
connected
to
the
igniter,
ho
ld
th
e
tip
ne
ar
the
ch
as
si
s
ground
and
at
te
m
pt
ig
ni
tio
n.
Is
a
spark
observed
between
the
igniter
and
ground?
--
-----i
YES
Replace
Burner
Remove
the
gas
train
in
cl
ud
in
g
the
flue
transition.
Remove
the
burner
and
inspect.
Any
sign
of
damage
to
burner
su
rf
ac
e?
YES
Co
nne
ct
all
wires
and
ch
ec
k
for
se
cu
re
fit
Inspect
the
flue
way
along
the
sid
es
of
the
baffle
near
the
coil
for
bl
oc
ka
ge
s.
Is
there
an
y
apparent
debris
or
obstruction
of
the
flue
wa
y?
YES
Refer
to
the
Gas
Valve
Troubleshooting
Tree
13 - TROUBLE SHOOTING
PN 240011320 Rev. G 10/01/2021]