55
13 - TROUBLE SHOOTING
Error shows when
safet
y circuit is o
pen
.
Rem
ov
e J
13 connector fr
om control
module. Ch
eck fo
r c
ontinuit
y between
two pins c
onnected to two pink wires, is continuit
y a
vailable?
YES
NO
Replac
e Co
ntrol M
odule
Boiler
fir
ed without en
ough w
ater
flow
through h
eat
ex
chan
ger
. Heat
ex
chan
ger
is o
ver
h
eat
ed. Either
h
igh limit o
r h
eat
ex
chan
ger
tem
per
ature s
witch is o
pen
.
Check t
he fo
llowing:
•
Air in system
?
•
Ver
ify
water
flow in system
piping
•
Flush system
if w
ater
is dirty.
Is boiler
supply pipe (ab
ov
e h
eat
ex
chan
ger
) h
ot?
W
ait fo
r boiler
to
cool down.
YES
NO
Replac
e B
rok
en
S
witch
Unplug m
olex
connector o
n s
upply
tem
per
ature s
en
sor
. Ch
eck c
ontinuit
y
between
two pins o
n sen
sor (two
pins
connected
to
two
pink
wires)
.
Is c
ontinuit
y a
vailable?
YES
NO
Check fo
r loose c
onnections o
n
two pink wires o
n J
13 connector
,
supply sen
sor
, an
d safet
y
tem
per
ature s
witch.
YES
NO
Fix Lo
ose Co
nnections
Replac
e Wi
re Har
ness
Let
al
l z
ones
run u
ntil w
ater
tem
per
ature
drops.
Is Heat
Ex
chan
ger
s
urfac
e
hot?
YES
NO
Check h
igh limit
an
d surfac
e
tem
per
ature
switches
PN 240011320 Rev. G 10/01/2021]