47
11.2
Annual Shut Down Procedure
•
Follow instructions “To Turn Off Gas To Appliance”
unless
boiler is also used to supply domestic hot water. See
section 10.
• Drain system completely if system does not have antifreeze
when heating system is to remain out of service during
freezing weather.
• Drain condensate lines when boiler is to be exposed to
freezing temperatures.
WARNING
Following service procedures must be performed
by qualified service agent. Boiler owner shall not
attempt these steps. Failure to do so could result in
death or serious injury.
!
11.3
Annual Inspection and Cleaning of Boiler
Components
• Obtain Burner Inspection Kit. Follow kit instructions to
prepare for examination and cleaning.
• Burner and heat exchanger inspection and cleaning:
1.
Remove gasket and burner. Allow burner to clear
top lip of chassis.
2.
Remove any residual sleeve and/or gasket material
from removed burner.
3.
Clean burner using air hose directed into top of
burner opening to dislodge any debris in burner
ports. Inspect burner for foreign matter in flame
ports or inside burner. Remove foreign matter
by blowing with compressed air or vacuuming.
Replace burner if it cannot be cleaned or is showing
deterioration.
4.
Clean heat exchanger with low pressure water
spray. Use flexible handle nylon brush to loosen
sediment and oxide on all accessible heating
surfaces of heat exchanger. Take care not to get
brush stuck in heat exchanger.
5.
Remove any remaining loosened sediment using
shop vacuum with snorkel attachment.
•
Clean condensate collector if significant debris found in heat
exchanger.
1.
Expand upper spring tension clip of condensate trap
using hose clamp pliers. Disconnect condensate trap
from condensate collector. See figure 9-1.
2.
Disconnect wire harness from vent temperature
sensor. See figures 3-4 & 3-5 .
3.
Loosen upper hose clamp securing condensate
collector to flue pipe using 3/8" socket with 6"
extension.
11 - GENERAL MAINTENANCE AND CLEANING
• Circulator pump and combustion air blower motor furnished
with boiler are permanently lubricated from factory and
require no further lubrication. Lubricate field sourced
pumps and/or motors according to pump and/or motor
manufacturer’s instruction.
• Check following components are operating properly and are
free of blockages or obstructions:
• air vent;
• check venturi air inlet for blockage and clean as
required;
• verify pressure test port cap and combustion test port
are in place;
• return temperature sensor clip must be securely seated
on pipe; Check boiler for any sign of leaks.
•
Check low water cutoff using user interface.
• Check operation by pressing test button on low water
cutoff.
• "Low Water" LED should illuminate and burner
should shut down.
• Should get error message on User Interface (E36).
•
Every 5 years remove low water cutoff. Reinstall after
cleaning.
•
Every 10 years replace low water cutoff.
•
See Table 13 page 40 for flame signal rate at 100% firing
rate ( High fire).
•
Visual inspection of flame through sight glass. Burner should
be fully illuminated. See
figures 11-1 & 11-2.
• Check heating system expansion tank.
PN 240011320 Rev. G 10/01/2021]