40
SECTION IX: ELECTRICAL
A.
GENERAL
1. Install wiring and electrically ground boiler in
accordance with requirements of the authority
having jurisdiction, or in absence of such
requirements the National Electrical Code, ANSI/
NFPA 70, and/or the CSA C22.1 Electric Code.
2. Refer to National Electric Code or Local Electric
Codes for proper size and type of wire required.
Follow Code.
3. A separate electrical circuit must be run from the
main electrical service with an over-current device/
disconnect in the circuit. A service switch is
recommended and may be required by some local
jurisdictions.
4. Use anti-short bushings on all wiring passing
through boiler jacket, junction boxes and/or control
boxes.
5. Use armored cable (BX) over all exposed line
voltage wiring.
6. If an indirect domestic water heater is used, use
priority zoning.
DO NOT
use priority zoning for
Hydro-Air Systems.
7. If boiler is installed in Canada, a blocked vent safety
switch must be installed. Refer to Blocked Vent
Safety Switch Instruction Supplement provided with
boiler (Canada only).
8. Wiring should conform to Figures 21A through 25.
B. INSTALL A ROOM THERMOSTAT
on an
inside wall about four feet above floor. Never install
thermostat on an outside wall or where it will be
influenced by drafts, hot or cold water pipes, lighting
fixtures, television, rays of the sun or near a fireplace.
Keep large furniture away from thermostat so there will
be free movement of room air around this control.
Heat Anticipator in Thermostat should be set to match
the requirements of the control to which it is connected.
See Figures 21A thru 25 for desired system and heat
anticipator setting. If system tends to overheat above
the thermostat's temperature setting, reduce heat
anticipator setting by .1 or .2 amps. If system tends to
short cycle without reaching desired room temperature,
increase heat anticipator setting by .1 or .2 amps.
DANGER
Positively assure all electrical connections are unpowered before attempting installation or service of
electrical components or connections of the boiler or building. Lock out all electrical boxes with padlock
once power is turned off.
WARNING
The primary control may be damaged or may not function properly if 120 volt power supply is NOT wired into
control as follows:
The 120V interrupted hot (black) wire must be connected to the primary control black wire, the 120V neutral
(white) wire must be connected to the primary control white wire and the 120V constant hot (red) wire must
be connected to the primary control red wire.
WARNING
Failure to properly wire electrical connections to the boiler may result in serious physical harm.
Electrical power may be from more than one source. Make sure all power is off before attempting any
electrical work.
Each boiler must be protected with a properly sized fused disconnect.
Never jump out or make inoperative any safety or operating controls.
Содержание V8H SERIES
Страница 76: ...76 Bare Boiler Assembly Continued SECTION XVI Repair Parts continued ...
Страница 78: ...78 Jacket Assembly SECTION XVI Repair Parts continued ...
Страница 80: ...80 V8H3 Thru V8H9 Steam Boilers Trim and Controls SECTION XVI Repair Parts continued ...
Страница 82: ...82 V8H3 Thru V8H9 Water Boilers Trim and Controls SECTION XVI Repair Parts continued ...
Страница 84: ...84 Beckett AFG Burner SECTION XVI Repair Parts continued ...
Страница 94: ...94 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 95: ...95 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 96: ...96 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...