SERVICE MODE Menu
44
PKG-SVP01E-EN
Condenser Fan Speed
Used With: Air-cooled units.
Factory Presets: 0%
Possible Values: AUTO, 0-100%
Ckt 1 0 %
1.
Press the NEXT key until the following screen is displayed
Condenser Fan Speed
Used With: Air-cooled units.
Factory Presets: 0%
Possible Values: AUTO, 0-100%
Ckt1 0% Ckt2 0%
1.
Press the NEXT key to advance the cursor.
2.
Press the NEXT key until the following screen is displayed
Compressor Relays:
Factory Presets: Off
Possible Values: On, Off
K11 OFF K3 OFf K12 OFF K4 OFF
1.
Press the NEXT key to advance the cursor.
2.
Press the NEXT key until the following screen is displayed
Hydronic Heat
Used With: Units when Hydronic heat is installed.
Factory Presets: 0%
Possible Values: 0 - 100%, AUTO
Actuator
0 %
1.
Press the NEXT key until the following screen is displayed.
Heat Stages
Used With: All Units when electric Heat is installed
Factory Presets: OFF
Possible Values: OFF, ON
Stage OFF
1.
Press the NEXT key until the following screen is displayed.
Note:
Only single stage electric heat is available factory installed.
OA Damper Pos 0%
Used With: All units with an airside economizer.
Factory Presets: OA Damper = 0%
Possible Values: OA Damper: 0 to 100%
1.
Press the NEXT key until the following screen is displayed.
Supply Fan Bypass Relay NORMAL
Used With: Units with VFD and bypass.
Possible Values: Normal, Bypass
1.
Press the NEXT key until the following screen is displayed.
Ventilation Override Module Output Relay
Used With: All Units when VOM is installed
Factory Presets: OFF
Possible Values: ON, OFF
OFF
1.
Press the NEXT key until the following screen is displayed.
OA Preheater State OFF
Used With: All Units when VCM is installed
Factory Presets: OFF
Possible Values: ON, OFF
1.Press the NEXT key to advance the cursor to the next field within this screen.
2.
Press the NEXT key until the following screen is displayed.
GBAS 0-5 VDC Module Relay Outputs
Used With: All Units when GBAS is installed
Factory Presets: OFF
Possible Values: 1, 2, 3, 4, 5 = ON, OFF
#1 OFF #2 OFF #3 OFF #4 OFF #5 OFF
1.
Press the NEXT key until the following screen is displayed.
Status/Annunc Test Sys On (Blinking)
Used With: All Units
Factory Presets: OFF
Possible Values: HEAT = ON, OFF, COOL = ON,
OFF, SERVICE = ON, OFF
Heat: OFF
Cool: OFF
Service: OFF
1.
Press the NEXT key to advance the cursor to the next field within this screen.
2.
Press the NEXT key until the following screen is displayed.
Start Test In 5 Seconds
Press TEST START To Begin, STOP To Halt
1.
Press the NEXT key to advance the cursor to the next field within this screen.
2.
Press the NEXT key until the following screen is displayed.