Programming Status
PKG-SVP01E-EN
17
Active Outside Air Humidity
30%
Used With: Units with an airside economizer only.
Possible Values: 0-100%
ECEM Return Air Humidity
62%
1.
Pressing the NEXT key will scroll forward through the screens.
End of Submenu (NEXT) to Enter SETUP
1.
Pressing the NEXT key will scroll forward through the screens.
Controlling Setpoint Status Submenu
Press ENTER to View Data in This Submenu
1.
Pressing the NEXT key will scroll forward through the screens.
Active Supply Air Cooling STP From
Used With: All VAV units only.
Possible Values: HI (Keypad) Setpoint Menu, Zone
Sensor Setpoint Input, GBAS 0-5 VDC Module, ICS
(Tracer Summit™)
HI (KEY PAD)
SETPOINT MENU
Is 55 F
1.
Pressing the NEXT key will scroll forward through the screens.
Active Supply Air Heating STP From
Used With: All VAV units only.
Possible Values: HI (Keypad) Setpoint Menu, Zone
Sensor Setpoint Input, GBAS 0-5 VDC Module, ICS
(Tracer Summit™)
HI (KEY PAD)
SETPOINT MENU
Is 100 F
1.
Pressing the NEXT key will scroll forward through the screens.
Active Daytime Warmup Setpoints
Used With: Units with hydronic, electric, or external
heat only.
Possible Values: HI (Keypad) Setpoint Menu
Initiate: 67 F
is Terminate
71 F
1.
Press the NEXT key until the following screen is displayed.
Active Occupied Zone Cooling STP From
Possible Values: HI (Keypad) Setpoint Menu, Zone
Sensor Setpoint Input, NSB Zone Sensor Setpoint
Input, GBAS 0-5 VDC Module, ICS (Tracer Summit™)
RTM ZONE TEMP INPUT
is 74 F
1.
Pressing the NEXT key will scroll forward through the screens.
Active Occupied Zone Cooling STP From
Used With:Units with hydronic, electric, or external
heat with daytime warmup enabled only).
Possible Values: HI (Keypad) Setpoint Menu, Zone
Sensor Setpoint Input, NSB Zone Sensor Setpoint
Input, GBAS 0-5 VDC Module, ICS (Tracer Summit™)
RTM ZONE TEMP INPUT is
100 F
1.
Pressing the NEXT key will scroll forward through the screens.
Active Unoccupied Zone Cooling STP From
Possible Values: HI (Keypad) Setpoint Menu, Zone
Sensor Setpoint Input, NSB Zone Sensor Setpoint
Input, GBAS 0-5 VDC Module, ICS (Tracer Summit™)
RTM ZONE TEMP INPUT is
85 F
1.
Pressing the NEXT key will scroll forward through the screens.
Used With:Units with hydronic, electric, or external
heat.
Possible Values: HI (Keypad) Setpoint Menu, Zone
Sensor Setpoint Input, NSB Zone Sensor Setpoint
Input, GBAS 0-5 VDC Module, ICS (Tracer Summit™)
Setpoint Range: 50-90 F
Active Unoccupied Zone Heating STP From
RTM ZONE TEMP INPUT is
60 F
1.
Pressing the NEXT key will bypass this section.
Active Morning Warmup Setpoint From
Used With:Units with hydronic, electric, or external
heat only.
Possible Values: HI (Keypad) Setpoint Menu, Zone
Sensor Setpoint Input, NSB Zone Sensor Setpoint
Input, GBAS 0-5 VDC Module, ICS (Tracer Summit™)
Setpoint Range: 50-90 F
HI (KEYPAD) SETPOINT MENU is
72 F
1.
Pressing the NEXT key will scroll forward through the screens.