40
PKG-SVP01E-EN
Programming Configuration
The electronically controlled unit has many operating
functions whose settings are preset at the factory. The
following configuration programming steps are provided
for those cases where the Human Interface module has
been replaced after the unit has been in operation and
must be reconfigured.
Refer to the Model number stamped on the unit nameplate
located on the control panel door while scrolling through
the configuration screens. Certain digits of this alpha/
numeric model number provide information that must be
entered at the Human Interface (HI) in order for the UCM
network to operate properly.
Note:
Many of the screens displayed in this section are
applicable only for the options that are installed in
the unit and may not be visible on your unit.
Press the CONFIGURATION key to begin viewing or
modifying the configuration screens.
Note:
Pay close attention to the notes throughout this
section of the document. The notes describe
additional essential messages and other
intermediate screen information.
Press the CONFIGURATION key to begin viewing or
modifying the unit setpoints.
To change the sepoint values on a particular screen:
1.
Press the plus or minus key until the correct value
appears in the screen.
2. Press the ENTER key to confirm your choice. If you’ve
made an error, press the CANCEL key to delete your
entry.
To navigate to another screen:
1.
Press the NEXT key to advance to the next screen, or
a. if no further changes are required and you want to
exit back to view the unit operating status, press the
STATUS key once, or
b. if you want to remain in the Setpoint submenu,
press the CONFIGURATION key once and it will
return you to the beginning of that particular
submenu, or
c. if you want to exit to another submenu in the in the
CONFIGURATION menu, press the
CONFIGURATION key twice. Then press the NEXT
key to scroll through the CONFIGURATION
submenu choices, or
d. if you want to exit to another menu, such as
SETPOINT, press that key once, then press the
NEXT key toscroll through those screens.
Configuration - Model Num Digit 1
Unit Type: Commercial Self-Contained
Used With: All Units
Possible Values: Commercial Self-Contained
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 3
Condenser Medium: WATER COOLED CONDENSER
Used With: All Units.
Possible Values: Water-cooled Condenser; Air-
colled condenser; None-No Condenser
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 4
Development Type: SIGNATURE SERIES
Used With: All Units.
Possible Values: Signature Series, Modular Series
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 5
Refrig Ckt Config INDEPENDENT
Used With: All Units
Possible Values: Independent, Manifold
Note:
Manifolded piping is only available on Signature Series units, 30 tons and larger
Configuration - Model Num Digit 27
Water Economizer INSTALLED
Possible Values: Installed, Not Installed
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 29
Water Piping: INTERMEDIATE PIPING
Used With: Units on all water-cooled units or units
with waterside economizer.
Possible Values: Intermediate Piping; Basic Piping;
Non-No Piping
1.
Press the NEXT key until the following screen is displayed.