Programming SETUP
28
PKG-SVP01E-EN
OA flow Compensation Function:
DISABLED
Used with: All Units when an airside
economizer and IGV or VFD is installed.
Possible Values: ENABLED, DISABLED
Enabled 2nd line= "OA Damper Min Pos
Depends on IGV/VFD Pos.; Disabled 2nd line=
"Use Fixed OA Damper Minimum Position"
Use fixed OA Damper Minimum Position
1.
Press the NEXT key until the following screen is displayed.
OA Flow CO
2
Reset Function: ENABLED
Used with: Units with a VCM
Possible Values: ENABLED, DISABLED
1.
Press the NEXT key until the following screen is displayed.
OA Flow CO
2
Reset Function: ENABLED
Used with: Units with a VCM installed and CO
2
reset enabled.
Possible Values: ENABLED, DISABLED; CO2
Start = 0-1900 PPM; CO2 Max = 100-2000 PPM
CO
2
Start: 800 PPM CO
2
Max: 1000 PPM
1.
Press the NEXT key until the following screen is displayed.
TRAQ Damper Quantity: 1
Used with: All Units when an airside
economizer with a Traq™ damper installed.
Possible Values: Quantity = 1-12; Size = 0,
13, 16, 20, 24, or 28
TRAQ Damper Size 28 Inches
1.
Press the NEXT key until the following screen is displayed.
OA Flow Calibration Data
Used with: Units with a VCM installed.
Factory Preset: Gain 1.0, Offset 0 CCFM
Possible Values: Gain= 0.5 to 1.5 (Default
1.0); Offset= -250 to 250 CCFM (Default 0 CFM)
Gain 1.0 Offset 0.0 CCFM
1.
Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1.
Press the NEXT key to leave the submenu and show following screen.
Ventilation Override Definitions
Ventilation Override Definitions
Used with: All Units when VOM is installed
Press ENTER to Review or Adjust
1.
Press the NEXT key until the following screen is displayed.
Ventilation Override Definition
Mode A
Used With: All Units when VOM and IGV or VFD
is installed
Factory Presets: Refer to Definitions
Possible Values: On, OFF
Supply Fan
ON
1.
Press the NEXT key until the following screen is displayed.
Ventilation Override Definition
Mode A
Used With: All Units when VOM and an airside
or waterside economizer is installed
Factory Presets: Refer to Definitions
Possible Values: OPEN/CLOSED
Outside Air Dampers
OPEN
1.
Press the NEXT key until the following screen is displayed.
Ventilation Override Definition
Mode A
Used With: All Units when VOM and electric or
hydronic heat is installed
Factory Presets: Refer to Definitions
Possible Values: Off/In Control
Heat
OFF
1.
Press the NEXT key until the following screen is displayed.
Ventilation Override Definition
Mode A
Used With: Units with a VOM
Factory Presets: Refer to Definitions
Possible Values: ENERGIZED/DEENERGIZED
VAV Box Relay
DEENERGIZED
1.
Press the NEXT key until the following screen is displayed.