Programming SETUP
PKG-SVP01E-EN
33
Actuator Setup
Water Economizer
Used With: All Units when a waterside
economizer is installed.
Factory Presets: 150 Sec
Possible Values: 1-255 Sec
Max Stroke Time
150 Sec
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup
Water Economizer
Used With: All Units when a waterside
economizer is installed.
Factory Presets: 2.0 VDC
Possible Values: 0-10 VDC
Min Voltage
2.0 VDC
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup
Water Economizer
Used With: All Units when a waterside
economizer is installed.
Factory Presets: 10.0 VDC
Possible Values: 0-10 VDC
Max Voltage
10.0 VDC
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup
Water Economizer
Used With: All Units when a waterside
economizer is installed.
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse Acting
Direct/Reverse Acting
Direct Acting
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup
Water Econ Bypass
Used With: All Units when a waterside
economizer is installed.
Factory Presets: 150 Sec
Possible Values: 1-255 Sec
Max Stroke Time
150 Sec
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup
Water Econ Bypass
Used With: All Units when a waterside
economizer is installed.
Factory Presets: 2.0 VDC
Possible Values: 0-10 VDC
Min Voltage
2.0 VDC
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup
Water Econ Bypass
Used With: All Units when a waterside
economizer is installed.
Factory Presets: 10.0 VDC
Possible Values: 0-10 VDC
Max Voltage
10.0 VDC
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup
Water Econ Bypass
Used With: All Units when a waterside
economizer is installed.
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse Acting
Direct/Reverse Acting
Direct Acting
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup IGV/VFD Cmd
Used With: All Units when IGV/VFD is installed
Factory Presets: 150 Sec
Possible Values: 1 - 255 Seconds
Max Stroke Time
150 Sec
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup IGV/VFD Cmd
Used With: All Units when IGV/VFD is installed
Factory Presets: 2.0 VDC
Possible Values: 0 to 10 VDC
Min Voltage
2.0 VDC
Note:
Min. voltage should be set to 2.0 on units with IGV.
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup IGV/VFD Cmd
Used With: All Units when IGV/VFD is installed
Factory Presets: 10.0 VDC
Possible Values: 0 to 10.0 Volts DC
Max Voltage
10.0 VDC
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup IGV/VFD Cmd
Used With: All Units when IGV/VFD is installed
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING, REVERSE
ACTING
Direct/Reverse Act
DIRECT ACTING
1.
Press the NEXT key until the following screen is displayed.