Programming Configuration
PKG-SVP01E-EN
41
Configuration - Model Num Digit 29
Water Flow Switch INSTALLED
Used With: Units on all water-cooled units or units
with waterside economizer and water flow switch.
Possible Values: Installed, Not Installed
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 20
Heating Type: HYDRONIC
Possible Values: Hydronic, Electric None, External
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 6, 7
Unit Capacity 72
Used With: All Units
Possible Values: 20-80
1.
Press the NEXT key until the following screen is displayed.
Note:
The possible value for unit capacity is dependent oupon the unit size (tons).
Configuration - Model Num Digit 23
Power Exhaust NONE
Used With: All Units
Possible Values: None, 100% with Statitrac, 50%/
100% without Statitrac
1.
Press the NEXT key until the following screen is displayed.
Note:
This option is currently not available on commercial self-contained units, but this screen still displays..
Configuration - Model Num Digit 28
Air Economizer INSTALLED
Used With: All Units
Possible Values: Installed, Not Installed
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 9
Air Temp/Vol Ctrl SA CTRL WITH IGV/VFD
Used With: All Units
Possible Values: SA Control with IGV/VFD, Zone
Control, No IGV/VFD or SA Control, No IGV/VFD
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 9
Supply Fan VFD Bypass INSTALLED
Used With: Units with SA Control and IGV/VFD
Possible Values: Installed, Not Installed
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 28
Comparative Enthalpy INSTALLED
Used With: All IntelliPak™ II Units
Possible Values: Installed, Not Installed
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 33
GBAS 0-5 VDC Module INSTALLED
Used With: All Units
Possible Values: Installed, Not Installed
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 33
Ventilation Override (VOM) INSTALLED
Used With: All Units
Possible Values: Installed, Not Installed
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 28
Ventilation Ctrl TRAQ DAMPERS
Used With: All Units
Possible Values: Traq™ Dampers, Standard
Dampers
1.
Press the NEXT key until the following screen is displayed.
Configuration - Model Num Digit 33
TCI4 Communications Module INSTALLED
Used With: All Units
Possible Values: nstalled, Not Installed
1.
Press the NEXT key until the following screen is displayed.