Programming Status
PKG-SVP01E-EN
19
Active OA Temperature Sensor Input From
RTM OUTSIDE AIR TEMP INPUT
is 86.0 F
Possible Values: RTM Outside Air Temp Input, ICS
(Tracer Summit™)
1.
Pressing the NEXT key will scroll forward through the screens.
Active Outside Air Humidity Sensor Input From
Used With: Units with an airside economizer.
Possible Values: O/A Humidity Sensor Input, ICS
(Tracer Summit™)
Sensor Range: 0 - 100%
OA HUMIDITY SENSOR INPUT
Is 30%
1.
Pressing the NEXT key will scroll forward through the screens.
Active Supply Air Press Sensor Input From
Used With: Units with IGV, VFD or with the SAP
sensor enabled
Possible Values: RTM SA PRessure Input, ICS
(Tracer Summit™)
RTM SA PRESSURE INPUT is
2.1 IWC
1.
Pressing the NEXT key will scroll forward through the screens.
Temp Sensor Input Being Monitored
Possible Values: RTM Zone Temp Input, NSB Zone
Sensor Setpoint Input, RTM Aux Temp Input, ECEM
return Air Temp Input, ICS (Tracer Summit™)
Sensor Range: -40 to 200 F
RTM ZONE TEMP INPUT is
82.0 F
1.
Pressing the NEXT key will scroll forward through the screens.
End of Submenu (NEXT) to Enter SETUP
1.
Press the NEXT key until the following screen is displayed. (if applicable)
Temperature Input Status Submenu
Press ENTER to View Data in This Submenu
1.
Pressing the NEXT key will scroll forward through the screens.
Temp Meausured By Sensor Connected To
RTM ZONE TEMP INPUT
82.0 F
1.
Press the NEXT key until the following screen is displayed. (if applicable)
Temp Meausured By Sensor Connected To
RTM SUPPLY AIR TEMP INPUT
50.0 F
1.
Press the NEXT key until the following screen is displayed. (if applicable)
Temp Measured By Sensor Connected To
NSB Panel Temp Sensor Input
79.5 F
Used With: Units with NSB zone sensor installed.
1.
Press the NEXT key until the following screen is displayed. (if applicable)
Temp Measured By Sensor Connected To
RTM AUX TEMP INPUT
62.0 F
1.
Press the NEXT key until the following screen is displayed.
Temp Measured By Sensor Connected To
RTM OUTSIDE AIR TEMP INPUT
86.0 F
1.
Press the NEXT key until the following screen is displayed.
Temp Measured By Sensor Connected To
HEAT MODULE AUX TEMP INPUT
82.0 F
Used With: Units with hydronic, electric, or
external heat only
1.
Press the NEXT key until the following screen is displayed. (if applicable)
Temp Measured By Sensor Connected To
ECEM RETURN AIR TEMP INPUT
78.0 F
Used With: Units with a VCM and OA preheater
enabled.
1.
Press the NEXT key until the following screen is displayed.