Programming Status
STATUS Menu
The STATUS menu is used to view various operating
conditions such as temperatures and humidity levels. It’s
used to view unit component status such as fan,
compressor, heater, and economizer operation, as well as
SETPOINT status.
The screens shown in this section are for example only.
Pressing the + (Plus) key while viewing any of the status
display screens will add that screen to the Custom menu.
When a status screen is displayed for 30 minutes without
a key being pressed, the LCD screen will revert to the
general operating status display. If this happens, press the
STATUS key again to return to the status menu. The
following are examples of status screens that may be
viewed by pressing the STATUS key.
Note:
Many of the screens displayed in this section are
applicable only for the options that are installed in
the unit and may not be visible on your unit.
Press the STATUS key to begin viewing the status screens.
Note:
The range for all temperature inputs is –40 to 200 F.
“ERR” will appear if the temperature is out of
range.
VAV OA FLOW
OCCUPIED
350.0 CCFM
OA DMPR 0%
SUPPLY FAN ON
DIAGNOSTICS
1.
Press the NEXT key until the following screen is displayed.
General System Status Submenu
Press ENTER to View Data in this Submenu
1.
Pressing the NEXT key will bypass this section.
RTM Supply Fan Relay:
RTM Supply Airflow Proving:
OFF
FLOW
Possible Values: Fan = On, Off
Airflow = Flow, No Flow
1.
Pressing the NEXT key will scroll forward through the screens.
2.
Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.
3.
Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the creation and maintenance
of customized menus.
4.
Press the NEXT key until the following screen is displayed. (if applicable)
IGV/VFD Cmd
Active Supply Air Pressure
30%
2.0 IWC
Used With: All units with IGV/VFD.
Possible Values: Increasing to: 0-100%;
Decreasing 100-0%
1.
Press the NEXT key until the following screen is displayed.
OR
Active Supply Air Pressure
2.0 IWC
Used With: Units without IGV/VFD.
1.
Press the NEXT key until the following screen is
displayed.
OR
WSM Water Pump Relay Status:
Active Water Flow Indication
OFF
Flow
Used With: Water-Cooled units only
Possible Values: Pump Status = Off, On Waterflow
= Flow, No Flow
1.
Press the NEXT key until the following screen is displayed.
Electric Heat
Stage 1 OFF
ENABLED
Stage 2 OFF
Stage 3 OFF
Used With: Units with Electric Heat
Possible Values: ON, OFF
1.
Press the NEXT key until the following screen is displayed. (if applicable)
Note:
Two or three stage electric heat is a field-provided option
Hydronic Heat:
Low Air Temp Limit
ENABLED
OK
0%
Used With: Units with hydronic heat only
Possible Values: Hydronic Heat = Enabled,
Disabled; Valve position = 0-100% open; Low temp
air = OK, tripped
1.
Press the NEXT key until the following screen is displayed.