Programming SETUP
32
PKG-SVP01E-EN
Device Charatcteristic Setup Definitions
To change device characteristics values on a particular
screen:
1.
Press the plus or minus key until the correct value
appears in the screen.
2. Press the ENTER key to confirm your choice. If you’ve
made an error, press the CANCEL key to delete your
entry.
To navigate to another screen:
1.
Press the NEXT key to advance to the next screen or
a. if no further changes are required and you want to
exit back to view the unit operating status, press the
STATUS key once, or
b. if you want to remain in the Device Characteristics
Setup Dfinitions submenu, press the SETUP key
once and it will return you to the bginning of that
particular submenu, or
c. if you want to exit to another submenu in the SETUP
menu, press the SETUP key twice. Then press the
NEXT key to scroll through the SETUP choices, or
d. if you want to exit to another menu, such as
CONFIGUREATION, press that key once, then press
the NEXT key to scroll through those screens.
Temperature Calibration Offset For
Used With: Water-cooled units and /or units
with waterside economizer is installed
Factory Presets: 0.0 F
Possible Values: 0.0-5.0 F
Ckt 2 Sat Cond Temp Input
0.0 F
1.
Press the NEXT key until the following screen is displayed.
Temperature Calibration Offset For
Used With: Water-cooled units and /or units
with waterside economizer is installed
Factory Presets: 0.0 F
Possible Values: 0.0-5.0 F
Ckt 3 Sat Cond Temp Input
0.0 F
1.
Press the NEXT key until the following screen is displayed.
Temperature Calibration Offset For
Used With: Water-cooled units and /or units
with waterside economizer is installed
Factory Presets: 0.0 F
Possible Values: 0.0-5.0 F
Ckt 4 Sat Cond Temp Input
0.0 F
1.
Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1.
Press the NEXT key to leave the submenu and show following screen.
Device Characteristic Setup Definitions
Used with: All Units
Press ENTER to review or Adjust
1.
Pressing the NEXT key will bypass this section.
Actuator Setup
OA Damper
Used With: All Units when an airside
economizer is installed.
Factory Presets: 150 Seconds
Possible Values: 1 - 255 Seconds
Max Stroke Time
30 Sec
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup
OA Damper
Used With: All Units when an airside
economizer is installed.
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 9.9 Volts DC
Min Voltage
2.0 VDC
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup
OA Damper
Used With: All Units when an airside
economizer is installed.
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts DC
Max Voltage
10.0 VDC
1.
Press the NEXT key until the following screen is displayed.
Actuator Setup
OA Damper
Used With: All Units when an airside
economizer is installed.
Possible Values: DIRECT ACTING, REVERSE
ACTING
Direct/Reverse Act
DIRECT ACTING
1.
Press the NEXT key until the following screen is displayed.