Programming Status
18
PKG-SVP01E-EN
Active Min OA Flow Setpoint from
Used With: Units with VCM module only
Possible Values: HI (Keypad) Setpoint Menu, GBAS
0-5 VDC Module
Setpoint Range: 0 to max unit airflow
REMOTE MIN POS POT INPUT
342.0 CFM
1.
Pressing the NEXT key will scroll forward through the screens.
Active Supply Air Pressure STP From
Used With: Units with IGV or VFD only.
Possible Values: HI (Keypad) Setpoint Menu, GBAS
Module
HI (KEYPAD SETPOINT MENU) is
2.0 IWC
1.
Pressing the NEXT key will scroll forward through the screens.
Active Supply Air Pressure Setpoints
Used With: Units with IGV or VFD only.
Possible Values: High Limit = 1.6-4.7 IWC;
Deadband = 0.1-2.0 IWC
Hi Limit: 40 IWC
Deadband: 0.5 IWC
1.
Pressing the NEXT key will scroll forward through the screens.
End of Submenu (NEXT) to Enter SETUP
1.
Pressing the NEXT key will scroll forward through the screens.
Controlling Sensor Status Submenu
Press ENTER to View Data in This Submenu
1.
Pressing the NEXT key will scroll forward through the screens.
Active Supply Air Heating Temp Sensor Input From
Possible Values: RTM Supply Air Temp Input, ICS
(Tracer Summit™)
RTM ZONE TEMP INPUT
is 50.0 F
1.
Pressing the NEXT key will scroll forward through the screens.
Active Daytime WU Temp Sensor Input From
RTM ZONE TEMP INPUT
is 82.0 F
Used With: Units with Electric, Hydronic or External
Heat installed.
Possible Values: RTM Zone Temp Input, NSB Zone
Sensor Setpoint Input, RTM Aux Temp Input, ECEM
return Air Temp Input, ICS (Tracer Summit™)
Sensor Range: -40 to 200 F
1.
Pressing the NEXT key will scroll forward through the screens.
Active Occupied Zone Temp Sensor Input From
Used With: Units with Electric, Hydronic or External
Heat with DWU installed.
Possible Values: RTM Zone Temp Input, NSB Zone
Sensor Setpoint Input, RTM Aux Temp Input, ECEM
return Air Temp Input, ICS (Tracer Summit™)
Sensor Range: -40 to 200 F
HI (KEYPAD) SETPOINT MENU
Is 90.0 F
1.
Pressing the NEXT key will scroll forward through the screens.
Active Unocc Zone Temp Sensor Input From
Possible Values: RTM Zone Temp Input, NSB Zone
Sensor Setpoint Input, RTM Aux Temp Input, ECEM
return Air Temp Input, ICS (Tracer Summit™)
Sensor Range: -40 to 200 F
RTM ZONE TEMP INPUT
is 75.0 F
1.
Pressing the NEXT key will scroll forward through the screens.
Active Morning WU Temp Sensor Input From
Used With: Units with Electric, Hydronic or External
Heat with MWU installed.
Possible Values: RTM Zone Temp Input, NSB Zone
Sensor Setpoint Input, RTM Aux Temp Input, ECEM
return Air Temp Input, ICS (Tracer Summit™)
Sensor Range: -40 to 200 F
RTM ZONE TEMP INPUT
is 82.0 F
1.
Pressing the NEXT key will scroll forward through the screens.
Active Zone Reset Sensor Input From
Possible Values: RTM Zone Temp Input, NSB Zone
Sensor Setpoint Input, RTM Aux Temp Input, ECEM
return Air Temp Input, ICS (Tracer Summit™)
Sensor Range: -40 to 200 F
RTM ZONE TEMP INPUT
is 82.0 F
1.
Pressing the NEXT key will scroll forward through the screens.