General Information
PKG-SVP01E-EN
11
No Configuration
If at power up the unit has not been programmed with the
necessary configuration data for normal unit operation,
the following display will appear on the Human Interface
LCD screen. When this screen is being displayed, the only
functional key is the CONFIGURATION key.
Note:
This screen will only appear when the RTM has
been field replaced. Refer to the Configuration
Menu.
Factory Presets
The UCM controlled unit has many operating functions
which are preset at the factory, but may be modified to
meet the unique requirements of each job. The following
list identifies each of the unit’s adjustable functions and the
value assigned to it. If these factory presets match the
application’s requirements, simply press the AUTO key at
the Human Interface module to begin unit operation (after
completing the Pre-Start and Start-Up procedures in the
Installation, Operation, and Maintenance manual). If the
application requires different settings, turn to the listed
page beside the function, press the designated function
menu key, then press and hold the NEXT or PREVIOUS key
until its screen appears on the LCD. Once the proper
screen appears, simply follow the programming
instructions given below the applicable screen in this
manual.
Note:
Record any changes made to the factory-preset
values in the corresponding space provided.
Table 3.
Factory presents
Adjustable Function
Factory Preset
Changed To
Reference Page
Control Parameters
Default system mode
Auto
Demand limit definition for cooling
None
Demand limit definition for heating
None
Economizer minimum position (w/o IGV or VFD)*
15%
Economizer minimum position with IGV @ 0%*
15%
Economizer minimum position with IGV @ 100%*
10%
Morning warm-up type
Full
Power-up start time delay
0 seconds
Supply air low limit*
50 °F
Supply air temperature deadband for cooling*
8 °F
Supply air temperature deadband for heating*
4 °F
Supply air temperature O/A reset start temp cooling
90 °F
Supply air temperature O/A reset end temp cooling
70 °F
Supply air temperature O/A reset start temp heating
10 °F
Supply air temperature O/A reset end temp heating
60 °F
Supply air temperature reset type cooling
none
Supply air temperature reset type heating
none
Supply air temperature zone reset start temp cooling
72 °F
Supply air temperature zone reset end temp cooling
69 °F
Supply air temperature zone reset start temp heating
65 °F
Supply air temperature zone reset end temp heating
68 °F
Supply air temperature reset max. amount cooling
5 °F
Supply air temperature reset max. amount heating
10 °F
Unit Address
1
Unit Control
Local