SETPOINT Menu
PKG-SVP01E-EN
39
For Default OA Damper Min Position, Use
Used With: All Units when an airside or
waterside economizer or VCM is installed.
Factory Presets: HI (KEYPAD) SETPOINT
MENU
Possible Values: HI (KEYPAD) SETPOINT
MENU, REMOTE MIN POS POT INPUT
Setpoint From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Min Outside Air Flow Rate Ctrl, Use
Used With: Units with a VCM or GBAS installed.
Factory Presets: HI (KEYPAD) SETPOINT
MENU
Possible Values: HI (KEYPAD) SETPOINT
MENU, GBAS 0-5VDC Module
Setpoint From: HI (KEYPAD) SETPOINT MENU
1.
Press the NEXT key until the following screen is displayed.
For Supply Air Pressure Control, Use
Used With: AUnits with a IGV or VFD and GBAS
installed.
Factory Presets: HI (KEYPAD) SETPOINT
Menu
Possible Values: HI (KEYPAD) SETPOINT
MENU, GBAS 0-5VDC Module
Setpoint From: HI(KEYPAD) SETPOINT Menu
1.
Press the NEXT key until the following screen is displayed (if applicable)
Used With: All units.
End Of Submenu (NEXT) To ENTER SETUP
1.
Press the NEXT key to leave the submenu and show following screen.