General Information
12
PKG-SVP01E-EN
Default Setpoint Setups
Daytime warmup - initiate
67 °F
Daytime warmup - terminate
71 °F
Low ambient compressor lockout (std. units)
50 °F
Supply air temp - cooling
55 °F
Supply air temp - heating
100 °F
Unoccupied zone time - cool
85 °F
Unoccupied zone temp - heat
60 °F
Unoccupied zone temp - MWU
72 °F
Function (Enable/Disable) Setups
Compressor lead/lag
Disable
Daytime warmup
Disable
Morning warmup
Enable
Supply air tempering
Disable
Unoccupied economizer
Enable
Unoccupied heating
Enable
Unoccupied mechanical cooling
Enable
Module Defaults
GBAS input/output assignments
GBAS input/output
not assigned
Information format
Text displays
Unit displays
English
English
Reference Enthalpy
25 btu/lb.
RTM alarm output assignments
any active diagnostic
Sensor source selection for:
Daytime warmup
RTM zone temp
Monitor Specified Temp. Input
RTM zone temp
Morning warmup
RTM zone temp
Unoccupied zone control
RTM zone temp
Zone reset
RTM aux temp
Setpoint source selection for:
Cooling supply air temp
default
Heating supply air temp
default
Morning warmup
default
Unoccupied zone cooling
default
Unoccupied zone heating
default
Actuator setup:
Direct/reverse action
direct acting
Max stroke time
150 seconds
Max voltage
10 VDC
Min voltage
2 VDC
Coil frost cutout temperature
30 °F
Condenser temperature control band:
Table 3.
Factory presents (continued)
Adjustable Function
Factory Preset
Changed To
Reference Page