background image

Programming SETUP

34

PKG-SVP01E-EN

Actuator Setup

Hydronic

Used With: All Units when Hydronic Heat is 
installed.
Factory Presets: 150 Seconds
Possible Values: 1 - 255 Seconds

Max Stroke Time

150 Sec

1.

Press the NEXT key until the following screen is displayed.

Actuator Setup

Hydronic

Used With: All Units when Hydronic Heat is 
installed.
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 9.9 Volts DC

Min Voltage

2.0 VDC

1.

Press the NEXT key until the following screen is displayed.

Actuator Setup

Hydronic

Used With: All Units when Hydronic Heat is 
installed.
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts DC

Max Voltage

10.0 VDC

1.

Press the NEXT key until the following screen is displayed.

Actuator Setup

Hydronic

Used With: All Units when Hydronic Heat is 
installed. 
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING, REVERSE 
ACTING

Direct/Reverse Act

DIRECT ACTING

1.

Press the NEXT key until the following screen is displayed.

 

Actuator Setup                                  Num 1 Low Ambient

Used With: Air-cooled units low ambient 
damper installed.
Factory Presets: 60 Seconds
Possible Values: 1 - 255 Seconds

Max Stroke Time

60 Sec

1.

Press the NEXT key until the following screen is displayed.

Actuator Setup                                  Num 1 Low Ambient

Used With: Air-cooled units low ambient 
damper installed.
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 9.9 Volts DC

Min Voltage

2.0 VDC

1.

Press the NEXT key until the following screen is displayed.

Actuator Setup                                  Num 1 Low Ambient

Used With: Air-cooled units low ambient 
damper installed.
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts DC

Max Voltage

10.0 VDC

1.

Press the NEXT key until the following screen is displayed.

Actuator Setup                                  Num 1 Low Ambient

Used With: Air-cooled units low ambient 
damper installed.
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse Acting

Direct/Reverse Act

DIRECT ACTING

1.

Press the NEXT key until the following screen is displayed.

Actuator Setup                                  Num 2 Low Ambient

Used With: Air-cooled units low ambient 
damper installed.
Factory Presets: 60 Seconds
Possible Values: 1 - 255 Seconds

Max Stroke Time

60 Sec

1.

Press the NEXT key until the following screen is displayed.

Actuator Setup                                  Num 2 Low Ambient

Used With: Air-cooled units low ambient 
damper installed.
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 9.9 Volts DC

Min Voltage

2.0 VDC

1.

Press the NEXT key until the following screen is displayed.

Actuator Setup                                  Num 2 Low Ambient

Used With: Air-cooled units low ambient 
damper installed.
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts DC

Max Voltage

10.0 VDC

1.

Press the NEXT key until the following screen is displayed.

Actuator Setup                                  Num 2 Low Ambient

Used With: Air-cooled units low ambient 
damper installed.
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse Acting

Direct/Reverse Act

DIRECT ACTING

1.

Press the NEXT key until the following screen is displayed.

Содержание IntelliPak SCRG-020

Страница 1: ...on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to the equipment IntelliPak Commercial Self Contained Signature Series 20 110Ton Modul...

Страница 2: ...nitor operating status set specific operating parameters and diagnose system problems Some screens shown in this manual are dependent on unit options and or model configuration Therefore some screens...

Страница 3: ...eens 13 Programming Status 14 STATUS Menu 14 Programming SETUP 22 SETUP Menu 22 SETUP Menu Screens 22 Sensor Source Selections Submenu 26 Outside Air Ventilation Setup 27 Ventilation Override Definiti...

Страница 4: ...uman Interface HO History Only Diagnostic HVAC heating ventilation and air conditioning ICS Integrated Comfort System IGV inlet guide vanes INFO Information Only Diagnostic I O input output Indep Inde...

Страница 5: ...ntrol module VDC volts DC Ventil ventilation VFD variable frequency drive Table 1 Acronyms continued VOM ventilation override module VVDA Variable Speed Fan VAV Discharge Air Temp Control W with w c w...

Страница 6: ...VOM can control the unit s air handling functions to perform customerspecified functions such as space pressurization exhaust purge unit off etc Interprocessor Communications Board IPCB Option The IP...

Страница 7: ...s below UNIT OFF sequence A When complete system shut down is required the following sequence can be used Supply fan Off Supply fan VFD Off 0 Hz if equipped Inlet guide vanes closed if equipped Outsid...

Страница 8: ...play Any steps that do not apply to all unit types are marked accordingly Ignore any steps that do not apply to your unit and or application Continue this process until all applicable screens are prog...

Страница 9: ...mode screens showing various unit components which may be turned on or off for the particular test being performed Once the status of these components is designated the LCD will display screens that...

Страница 10: ...nu press the CUSTOM key then press the NEXT key until the status screen that you want to remove appears then press the Minus key General Status Display Anytime the rooftop unit is powered up or the ST...

Страница 11: ...in this manual Note Record any changes made to the factory preset values in the corresponding space provided Table 3 Factory presents Adjustable Function Factory Preset Changed To Reference Page Cont...

Страница 12: ...ation format Text displays Unit displays English English p 22 p 22 Reference Enthalpy 25 btu lb p 37 RTM alarm output assignments any active diagnostic p 30 Sensor source selection for Daytime warmup...

Страница 13: ...temperature 0 F p 31 Outdoor air 0 F p 31 Ventilation override definitions N A p 28 Table 3 Factory presents continued Adjustable Function Factory Preset Changed To Reference Page Password Entry Time...

Страница 14: ...lay RTM Supply Airflow Proving OFF FLOW Possible Values Fan On Off Airflow Flow No Flow 1 Pressing the NEXT key will scroll forward through the screens 2 Pressing the PREVIOUS key will scroll backward...

Страница 15: ...nsor low ambient lockout demand limit ventilation override low ent cond water temp 1 Pressing the NEXT key will scroll forward through the screens Compressor Relay K12 Enabled OFF Used With Units with...

Страница 16: ...il the following screen is displayed Water Economizing DISABLED Used With Units with a waterside economizer only Possible Values Economizer Disable enable Water econ position opening to closing to 0 1...

Страница 17: ...Menu Zone Sensor Setpoint Input NSB Zone Sensor Setpoint Input GBAS 0 5 VDC Module ICS Tracer Summit RTM ZONE TEMP INPUT is 74 F 1 Pressing the NEXT key will scroll forward through the screens Active...

Страница 18: ...Possible Values RTM Zone Temp Input NSB Zone Sensor Setpoint Input RTM Aux Temp Input ECEM return Air Temp Input ICS Tracer Summit Sensor Range 40 to 200 F 1 Pressing the NEXT key will scroll forward...

Страница 19: ...ollowing screen is displayed if applicable Temperature Input Status Submenu Press ENTER to View Data in This Submenu 1 Pressing the NEXT key will scroll forward through the screens Temp Meausured By S...

Страница 20: ...72 0 Sat Cond Temp 87 0 F 1 Pressing the NEXT key will scroll forward through the screens Compressor Module Ckt 3 Used With SCWF SIWF 42 80 tons or SCRF SIRF 50 60 tons only Evap Temp 72 0 Sat Cond Te...

Страница 21: ...End of Submenu NEXT to Enter SETUP 1 Press the NEXT key until the following screen is displayed GBAS 0 5VDC Module Staus Submenu Press ENTER to View Data in This Submenu Used With Units with GBAS modu...

Страница 22: ...Press the SETUP key to begin viewing or modifying the SETUP screens If a screen is not visible on the Unit Human Interface Module refer to the UsedWith information listed to the right of each screen...

Страница 23: ...OINT Used With Units with VCM installed Factory Preset Control Disabled Possible Values Control Enabled Disabled 1 Press the NEXT key until the following screen is displayed Demand Limit Definition Co...

Страница 24: ...es SAT Zone OA Reset Zone 72 Reset OA 72 Maximum Amount of Reset Applied 5 F 1 Press the NEXT key until the following screen is displayed Supply Air Temp Outside Air Reset For Heating Used With All Un...

Страница 25: ...until the following screen is displayed End of Submenu NEXT to Enter SETUP 1 Press the NEXT key to leave the submenu and show following screen 2 Press PREVIOUS to page back through the submenu Water F...

Страница 26: ...mit 90 F 1 Press the NEXT key until the following screen is displayed Cond Temp Control Band Used With All air cooled units Factory Presets Upper 120 F Lower 80 F Possible Values Lower 70 F to 90 F Up...

Страница 27: ...INPUT NSB PANEL TEMP SENSOR INPUT RTM AUX TEMP INPUT HEAT MODULE AUX TEMP INPUT ECEM RETURN AIR TEMP INPUT Connected To RTM ZONE TEMP INPUT 1 Press the NEXT key until the following screen is displaye...

Страница 28: ...set 250 to 250 CCFM Default 0 CFM Gain 1 0 Offset 0 0 CCFM 1 Press the NEXT key until the following screen is displayed End of Submenu NEXT to Enter SETUP 1 Press the NEXT key to leave the submenu and...

Страница 29: ...ble Values ON OFF Supply Fan 1 Follow the preceding steps used to program MODE A to program MODE B C D and E if modifications are needed After all of the Ventilation Override Definitions have been pro...

Страница 30: ...er 1 assignment Plus key will assign ALL Diagnostics and Minus key will allow diagnostic selection 3 Press the ENTER key to confirm this choice If Yes was assigned to the Output assignment the output...

Страница 31: ...key until the following screen is displayed Temperature Calibration Offset For Used With All Units when Electric or Hydronic Heat is installed Factory Presets 0 0 F Possible Values Plus or Minus 5 0 F...

Страница 32: ...installed Factory Presets 0 0 F Possible Values 0 0 5 0 F Ckt 3 Sat Cond Temp Input 0 0 F 1 Press the NEXT key until the following screen is displayed Temperature Calibration Offset For Used With Wate...

Страница 33: ...sible Values 0 10 VDC Min Voltage 2 0 VDC 1 Press the NEXT key until the following screen is displayed Actuator Setup Water Econ Bypass Used With All Units when a waterside economizer is installed Fac...

Страница 34: ...Voltage 2 0 VDC 1 Press the NEXT key until the following screen is displayed Actuator Setup Num 1 Low Ambient Used With Air cooled units low ambient damper installed Factory Presets 10 0 VDC Possible...

Страница 35: ...lgorithmTuning Parameters Applicable to all units Control Algorithm Tuning Parameters Press ENTER to Review or Adjust Note Contact theTrane Company before making any adjustment to these settings 1 Pre...

Страница 36: ...to scroll through the SETPOINT submenu choices or d if you want to exit to another menu such as CONFIGURATION press that key once then press the NEXT key toscroll through those screens Default Supply...

Страница 37: ...r without an airside economizer with IGV or VFD and a VCM Factory Presets 15 Possible Values 0 100 With IGV VFD Command At Minimum 0 1 Press the NEXT key until the following screen is displayed Defaul...

Страница 38: ...NT MENU 1 Press the NEXT key until the following screen is displayed For Occ Zone Temp Heating Control Use Used With All Units with hydronic or electric heat Factory Presets HI KEYPAD SETPOINT MENU Po...

Страница 39: ...stalled Factory Presets HI KEYPAD SETPOINT MENU Possible Values HI KEYPAD SETPOINT MENU GBAS 0 5VDC Module Setpoint From HI KEYPAD SETPOINT MENU 1 Press the NEXT key until the following screen is disp...

Страница 40: ...press the STATUS key once or b if you want to remain in the Setpoint submenu press the CONFIGURATION key once and it will return you to the beginning of that particular submenu or c if you want to exi...

Страница 41: ...uration Model Num Digit 9 Air Temp Vol Ctrl SA CTRL WITH IGV VFD Used With All Units Possible Values SA Control with IGV VFD Zone Control No IGV VFD or SA Control No IGV VFD 1 Press the NEXT key until...

Страница 42: ...s with VOM module installed 1 Pressing the NEXT key will scroll forward through the screens Software Revision Number Report Exhaust Comp Enthalpy Module 8 04 Used With Units with Comparative Enthalpy...

Страница 43: ...e and it will return you to the beginning of that particular submenu or c if you want to exit to another submenu in the in the SERVICE MODE menu press the CONFIGURATION key twice Then press the NEXT k...

Страница 44: ...key until the following screen is displayed Supply Fan Bypass Relay NORMAL Used With Units with VFD and bypass Possible Values Normal Bypass 1 Press the NEXT key until the following screen is display...

Страница 45: ...r scrolling through the Active list or after pressing the DIAGNOSTICS key when no active diagnostics are present It s used to view the past 20 diagnostics Diagnostics in this log are stacked in invers...

Страница 46: ...ssure Occ Zone Heat Setpoint Return Air Temp Supply Air Pres RA Humidity OA Humidity Auto Reset SA Static Pres Limit SCM Communication Evap Temp CKT 1 2 3 4 MCM Communication Heat Module Commun ECEM C...

Страница 47: ...shoot diagnostics reference the Installation Operation and Maintenance Manual SCXF SVX01 EN that ships with the Signature Series units and SCXG SVX01 EN that ships with the Modular Series units Log 1...

Страница 48: ...TPOINT Suppression a parameter used for setting the ZoneTemp SETPOINT at a lower value than the mechanical cooling zone temp SETPOINT External Heat A heat source external to the self contained unit th...

Страница 49: ...e Pressure The pressure in the building as measured by the Space Pressure Transducer referenced to outside atmospheric pressure Supply Air Pressure High Limit A pressure limit to prevent unit casing a...

Страница 50: ...Generic Building Automation System 4 6 Glossary 48 H Heat Module 6 Human Interface 22 40 Human Interface Keypad See Figure 2 9 Human Interface Module See Figure 1 8 Hydronic Heat 48 I Independent Refr...

Страница 51: ...empering 49 T TCI 5 46 Temperature Input Calibration 30 Temperature Input Offset 13 30 TEST START 9 43 TEST START Key 10 Trane Communications Interface Module TCI Option 6 U UCM 5 6 UCM Control System...

Страница 52: ...controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and product data improvement and reserves the rig...

Отзывы: