Customer-Supplied Remote Starter Wiring
50
CVHH-SVX001A-EN
Current Transformer and Potential
Transformer Wire Sizing
For custom er-supplied starter-to-chiller unit control panel
starter m odule 1K23; these w ires m ust be separated from
120 Vac or higher w iring.
Table 15. M aximum recommended w ire length for
secondary CT leads in dual CT system
W ir e AW G
( a )
( a) For AWG/ MCM equivalent s in m m
2
, r efer t o
Table 12, p. 47
. Wires, lugs,
and fuses/ br eaker s are sized based on Nat ional Elect r ic Code NEC
[ NFPA 70] and UL 1995.
M a x im u m W ir e Le n gt h
Se con da r y CT Le a ds
M e t e r s
Fe e t
8
415.5
1362.8
10
261.2
856.9
12
164.3
538.9
14
103.3
338.9
16 65.0
213.1
17
51.5
169.1
18
40.9
134.1
20
25.7
84.3
Notes:
1 . Wir e lengt h is for copper conduct or s only.
2 . Wir e lengt h is t ot al one- w ay dist ance t hat t he CT can be fr om t he
st ar t er m odule.
Table 16. M aximum recommended total w ire length for
PTs in a single PT system
W ir e AW G
( a )
( a) For AWG/ MCM equivalent s in m m
2
, r efer t o
Table 12, p. 47
. Wir es, lugs,
and fuses/ br eaker s are sized based on Nat ional Elect r ic Code NEC
[ NFPA 70] and UL 1995.
M a x im u m Le a d Le n gt h
M e t e r s
Fe e t
8
1627
5339
10
1023
3357
12
643
2112
14
404
1328
16
254
835
17
201
662
18
160
525
20
100
330
21
79
262
22
63
207
Notes:
1 . Wir e lengt h is for copper conduct or s only.
2 . The above lengt h is m ax im um r ound t r ip w ir e lengt h. The m axim um
dist ance t he PT can be locat ed from t he st art er m odule is half of t he
list ed value.
Table 17.
M ax recommended total w ire length (to and
from) for PT leads in a dual PT system
W ir e
AW G
( a )
( a) For AWG/ MCM equiv alent s in m m
2
, r efer t o
Table 12, p. 47
. Wires, lugs,
and fuses/ br eaker s ar e sized based on Nat ional Elect r ic Code NEC
[ NFPA 70] and UL 1995.
M a x W ir e Le n gt h
Pr im a r y
M a x W ir e Le n gt h
Se con da r y
M e t e r s
Fe e t
M e t e r s
Fe e t
8
933
3061
217
711
10
586
1924
136
447
12
369
1211
85
281
14
232
761
53
177
16
145
478
33
111
17
115
379
26
88
18
91
301
21
70
20
57
189
13
44
21
45
150
10
34
22
36
119
8
27
Notes:
1 . Wir e lengt h is for copper conduct ors only.
2 . The above lengt h is m axim um r ound t r ip w ir e lengt h. The m axim um
dist ance t he PT can be locat ed fr om t he st ar t er m odule is half of t he
list ed value.