Installation: Water Piping
28
CVHH-SVX001A-EN
Victaulic Gasket Installation
1.
Inspect supplied gasket to be certain it is suited for
intended service (code identifies gasket grade). Apply
a thin coat of silicone lubricant to gasket tips and
outside of gasket.
2. Install gasket, placing gasket over pipe end and m aking
sure gasket lip does not overhang pipe end. Refer to
Figure 18
for gasket configuration.
3. Align and bring tw o pipe ends together and slide
gasket into position centered betw een the grooves on
each pipe. No portion of the gasket should extend into
the groove on either pipe.
4. Open fully and place hinged Victaulic flange around
the grooved pipe end w ith the circular key section
locating into the groove.
5. Insert a standard bolt through the m ating holes of the
Victaulic flange to secure the flange firm ly in the
groove.
6. Tighten fasteners alternately and equally until housing
bolt pads are firm ly together (m etal to m etal); refer to
“ Bolt-Tightening Sequence for Water Piping
Connections,” p. 29
. Do not excessively tighten
fasteners.
N ot e: Uneven tightening m ay cause gasket to pinch.
Figure 17.
M odifying 300 psig or 21 bar flange adaptors
for flat-faced flange application
Rem ove t o m at e
t o flat- faced
flanges
Figure 18.
Typical Victaulic flange gasket configuration
Table 6.
Installation data for 150 psig flange adapters (Style 741)
N om in a l Pipe Size
Asse m bly Bolt
Siz e
( a )
N u m be r of
Asse m b ly Bolt s
Re q u ir e d
Bolt Pa t t e r n D ia m e t e r
W e igh t
m m
in .
in .
m m
in .
k g
lb
200
8
3/ 4 x 3- 1/ 2
8
298
11.75
7.5
16.6
250
10
7/ 8 x 4
12
362
14.25
11
24.2
300
12
7/ 8 x 4
12
432
17
21.2
46.8
350
14
1 x 4- 1/ 2
12
476
18.75
28.1
62
400
16
1 x 4- 1/ 2
16
540
21.25
35.8
79
450
18
1- 1/ 8 x 4- 3/ 4
16
578
22.75
37.3
82.3
500
20
1- 1/ 8 x 5- 1/ 4
20
635
25
46.9
103.3
600
24
1- 1/ 4 x 5- 3/ 4
20
749
29.5
64.4
142
( a) Bolt size for conv ent ional flange t o flange connect ion. Longer bolt s are required w hen flange w asher m ust be used.
Table 7.
Installation data for 350 psig flange adapters (Style 743)
N om in a l Pipe Size
Asse m b ly Bolt
Siz e
( a )
N u m be r of
Asse m bly Bolt s
Re qu ir e d
Bolt Pa t t e r n D ia m e t e r
W e ig h t
m m
in .
in .
m m
in .
k g
lb
219.1
8
3/ 4 x 4- 3/ 4
12
330
13
15.6
34.3
273.0
10
1 x 5- 1/ 4
16
387
15.25
21.9
48.3
323.9
12
1- 1/ 8 x 5- 3/ 4
16
451
17.75
32.0
70.5
( a) Bolt size for conv ent ional flange t o flange connect ion. Longer bolt s are required w hen flange w asher m ust be used.
Содержание CVHH