![Trane CVHH Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/trane/cvhh/cvhh_installation-operation-and-maintenance-manual_1149664013.webp)
Pre-Installation
CVHH-SVX001A-EN
13
Storage Requirements
“ CenTraVac™ I nst allat ion
Com plet ion Check Sheet
and Request for Trane
Serv ice”
( CTV- ADF001- EN; r efer t o
“ For m s and Check Sheet s,”
p. 102
)
•
To be com plet ed by inst alling cont ract or pr ior t o
cont act ing Trane for st art - up
Chiller st ar t - up
com m issioning
( a)
•
Trane, or an agent of Trane
specifically aut hor ized t o
perfor m st art - up of Trane
®
pr oduct s
( a) St ar t - up m ust be per for m ed by Tr ane or an agent of Tr ane specifically aut horized t o per for m st ar t - up and w ar r ant y of Tr ane
®
product s. Cont r act or shall
pr ov ide Tr ane ( or an agent of Tr ane specifically aut hor ized t o per for m st ar t - up) w it h not ice of t he scheduled st ar t - up at least t w o w eeks prior t o t he
scheduled st art - up.
Type of
Re qu ir e m e n t
Tr a n e Su pplie d
Tr a n e I n st a lle d
Tr a n e Su pplie d
Fie ld I n st a lle d
Fie ld Su pplie d
Fie ld I n st a lle d
NOTICE:
Insulation Damage!
Do not expose unit to direct sunlight as it could result
in damage to factory-installed insulation.
Le ss t h a n 1 m on t h
1 – 6 m on t h s
Gr e a t e r t h a n 6 m on t h s
Locat ion r equir em ent s:
•
solid foundat ion
•
v ibrat ion fr ee
•
dr y
•
t em perat ur e range - 40°C t o 70°C
( - 40°F t o 158°F)
Locat ion r equir em ent s:
•
solid foundat ion
•
v ibrat ion free
•
dr y
•
t em perat ur e range - 40°C t o 70°C
( - 40°F t o 158°F)
Locat ion r equirem ent s:
•
solid foundat ion
•
v ibrat ion fr ee
•
dr y
•
t em perat ure range - 40°C t o 70°C
( - 40°F t o 158°F)
•
Do not r em ove any plast ic cover ings
•
Do not r em ove
any plast ic cover ings
•
Do not rem ove any plast ic cover ings
•
Do not charge t he chiller w it h refr igerant
•
I f addit ional refr igerant is on sit e, follow
m anufact ures st orage r equirem ent s
•
Do not charge t he chiller w it h refrigerant
•
I f addit ional refr igerant is on sit e, follow
m anufact ur es st orage r equirem ent s
•
Do not char ge t he chiller w it h r efr igerant
•
I f addit ional r efr igerant is on sit e, follow
m anufact ur es st orage requir em ent s
•
Ver ify dr y nit rogen pr essure using gauge
locat ed on t he evaporat or shell r eads
20.7 t o 34.5 k Pag ( 3 t o 5 psig)
•
Not ify t he local Trane office if char ge has
escaped
•
Verify dr y nit r ogen pr essur e using gauge
locat ed on t he evaporat or shell r eads
20.7 t o 34.5 k Pag ( 3 t o 5 psig)
•
Not ify t he local Trane office if char ge has
escaped
•
Ver ify dry nit r ogen pr essur e using gauge locat ed
on t he evaporat or shell r eads 20.7 t o 34.5 kPag
( 3 t o 5 psig)
•
Not ify t he local Trane office if char ge has escaped
•
Do not operat e pur ge unit
•
Do not operat e pur ge uni
t
•
Do not operat e purge unit
•
Verify wat er box and t ube bundles are
clean and dr y
•
Ver ify wat erbox and t ube bundles ar e clean and
dr y
•
Conduct an oil analy sis and ver ify no oil
br eakdow n
( a)
•
Repeat year ly
•
Replace oil if br eak dow n has occurr ed
•
I f no oil analy sis pr ogram has been follow ed,
r eplace oil prior t o st ar t up
Note: Chiller s st or ed 5 year s or longer should be inspect ed ever y 5 year s by a qualified ser v ice or ganizat ion for leak s.
( a) I f pr ot ect iv e plast ic cov er ings need t o be r em ov ed for access and/ or ser vice, cont act y our local Tr ane office.
Содержание CVHH
Страница 110: ......