Installation: M echanical
CVHH-SVX001A-EN
19
location, contact Trane. For m ore inform ation, refer to
“ Factory Warranty Inform ation,” p. 4
.
Unit Isolation
To m inim ize sound and vibration transm ission through the
building structure, and to ensure proper w eight
distribution over the m ounting surface, always install
isolation pads or spring isolators under the chiller feet.
N ot e: Isolation pads (see
Figure 6
) are provided w ith each
chiller unless spring isolators are specified on the
sales order.
Specific isolator loading data is provided in the unit
subm ittal package. If necessary, contact your local Trane
sales office for further inform ation.
Im port ant :
When determ ining placem ent of isolation
pads or spring isolators, rem em ber that the
control panel side of the unit is always
designated as the unit front.
Isolation Pads
When the unit is ready for final placem ent, position
isolation pads (457.2-m m sides) end for end under the full
length of the chiller leg. The pads m easure 228.6 m m x
457.2 m m (9 in. × 18 in.) and on som e units there m ay be
sm all gaps betw een pads. Pads are provided to cover
entire foot.
Rem em ber that the chiller m ust be level w ithin 1.6 m m
(1/16 in.) over its length and w idth after it is low ered onto
the isolation pads. In addition, all piping connected to the
chiller m ust be properly isolated and supported so that it
does not place any stress on the unit.
Spring Isolators
Spring isolators should be considered w henever chiller
installation is planned for an upper story location. Base
isolator placem ent is show n in
Figure 7
; also refer to
Table 3
.
Spring isolators typically ship assem bled and ready for
installation. To install and adjust the isolators properly,
follow the instructions given.
Figure 6.
Isolation pad and dimensions
228.6 m m
( 9 in.)
457.2 m m
( 18 in.)
9. 525 m m
( 3/ 8 in.)
Figure 7.
Isolation spring placement by shell size,
evaporator and condenser length
Table 3.
Isolation spring placement, cm (in.)
EV SZ
CD SZ
W id t h
Ev a p
W idt h Le n gt h
I sola t or
Con fig
Or igin
t o
Ce n t e r
of Re a r
Pa d
Or igin
t o
Ce n t e r
of
M id dle
Pa d
200L
200L
285.0
( 112.2)
170.2
( 67)
457.2
( 180)
2
268.5
( 105.7)
153.7
( 60.5)
220L
220L
303.3
( 119.4)
188.0
( 74)
457.2
( 180)
2
286.8
( 112.9)
171.5
( 67.5)
200L
20HL
336.0
( 132.3)
170.2
( 67)
457.2
( 180)
2
319.5
( 125.8)
153.7
( 60.5)
220L
22HL
361.0
( 142.5)
188.0
( 74)
457.2
( 180)
2
345.4
( 136)
171.5
( 67.5)
160M
20HM
323.3
( 127.3)
154.9
( 61)
406.4
( 160)
2
306.8
( 120.8)
138.4
( 54.5)
200L
220L
285.2
( 112.3)
170.2
( 67)
457.2
( 180)
2
268.7
( 105.8)
153.7
( 60.5)
160M
200M
270.3
( 106.4)
154.9
( 61)
406.4
( 160)
2
253.7
( 99.9)
138.4
( 54.5)
100M
100M
264.4
( 104.1)
N/ A
406.4
( 160)
1
247.9
( 97.6)
N/ A
100L
100L
264.4
( 104.1)
N/ A
457.2
( 180)
1
247.9
( 97.6)
N/ A
130M
130M
277.6
( 109.3)
N/ A
406.4
( 160)
1
261.1
( 102.8)
N/ A
100M
10HM
300.2
( 118.2)
N/ A
406.4
( 160)
1
283.7
( 111.7)
N/ A
130M
13HM
313.4
( 123.4)
N/ A
406.4
( 160)
1
296.9
( 116.9)
N/ A
Condenser
Evaporat or
Lengt h
2
5
1
4
6
3
Widt h
I sola t or Con figu r a t ion 1
Or igin:
Right fr ont corner of
evap r ight fr ont foot
Condenser
Evaporat or
Lengt h
2
5
1
4
6
3
Evap
Widt h
Widt h
I sola t or Con figu r a t ion 2