Installation: Water Piping
26
CVHH-SVX001A-EN
Water Piping Connections
All standard units use grooved-pipe connections. These
are grooved-end NSP (Victaulic style) pipe connections.
Flanged connections are optional.
Piping joined using grooved type couplings, like all types
of piping system s, requires proper support to carry the
w eight of pipes and equipm ent. The support m ethods
used m ust elim inate undue stresses on joints, piping and
other com ponents; allow m ovem ent w here required, and
provide for any other special requirem ents (i.e., drainage,
etc.).
N ot e: Plug-type sensor extension cables are available for
purchase from Trane Parts Service if needed. These
sensor extension cables m ay be necessary if the
waterboxes are changed or if the tem perature
sensors are m oved out into the unit piping for
better m ixed tem perature readings.
Waterbox Locations
If necessary, the non-m arine-style waterboxes on each
shell w hether evaporator or condenser can be sw itched
end-for-end to obtain the desired piping arrangem ent.
If rem oval of waterboxes is necessary, refer to
“ Waterbox
Rem oval and Installation,” p. 98
.
If the waterboxes on any of the shells are exchanged end-
for-end, be sure to reinstall them right side up to m aintain
the correct baffle arrangem ents. Use a new gasket w ith
each waterbox cover.
Table 4.
Water connection pipe sizes
W a t e r
Pa sse s
Sh e ll Siz e
1 0 0
1 3 0
1 6 0
2 0 0
2 2 0
4 0 0
4 4 0
Ev a por a t or
M e t r ic Pipe Siz e ( m m )
1 Pass
DN300
DN300
DN350
DN400
DN500
DN400
DN500
2 Pass
DN250
DN250
DN300
DN350
DN350
—
—
3 Pass
DN200
DN200
DN250
DN300
DN300
—
—
Con de n se r
1 Pass
DN300
DN350
—
DN400
DN600
—
DN600
2 Pass
DN250
DN300
—
DN350
DN350
—
—
Ev a por a t or
N om in a l Pipe Siz e ( in .)
1 Pass
12
12
14
16
20
16
20
2 Pass
10
10
12
14
14
—
—
3 Pass
8
8
10
12
12
—
—
Con de n se r
1 Pass
12
14
—
16
24
—
24
2 Pass
10
12
—
14
14
—
—
Figure 14.
Typical grooved pipe connection
NOTICE:
Do Not Exchange Positions of Heat
Recovery Waterboxes!
Failure to follow this instruction could prevent proper
unit operation. Contact CenTraVac Technical Service for
sw itching of heat recovery w aterboxes.