5.14 Preset-speed operation (15 speeds)
〜
:
Preset-speed #1 to #7
〜
:
Preset-speed #8 to #15
〜
:
Preset-speed #1 to #15 control mode
[Setting method]
1) Start/stop
Start and stop control is experienced by the control panel. (Default setting)
Title
Function
Adjustment range
Default setting
Operation command
mode selection
: Terminal block enabled
:
Operating panel enabled
:
Common serial communication option
: Serial communication RS485
:
Communication add-on cassette option
Note) When speeds commands (analog signal or digital signal input) need to be switched in a
preset-speed mode, then make a selection with the speed setting mode selection
parameter
.
=> Refer to 5.3 for details.
2) Setting preset-speed frequencies
A required number of speeds (frequencies) can be set.
Setting speeds 1 to 7
Title
Function
Adjustment range
Default setting
〜
Preset-speed #1 to #7
〜
Setting speeds 8 to 15
Title
Function
Adjustment range
Default setting
〜
Preset-speed #8 to #10
〜
Example of preset-speed contact input signal
0: ON, -: OFF (If all terminals are off , a speed command other than the preset speed commands is valid.)
Preset-speed
Terminal
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15
S1-CC
○
−
○
−
○
−
○
−
○
−
○
−
○
−
○
S2-CC
−
○
○
−
−
○
○
−
−
○
○
−
−
○
○
S3-CC
−
−
−
○
○
○
○
−
−
−
−
○
○
○
○
S4-CC
−
−
−
−
−
−
−
○
○
○
○
○
○
○
○
☆
Functions assigned to terminals (Default setting)
Terminal S1 ... Input terminal selection #5 (S1)
=
(S1)
Terminal S2 ... Input terminal selection #6 (S2)
=
(S2)
Terminal S3 ... Input terminal selection #7 (S3)
=
(S3)
Terminal S4 ... Input terminal selection #8 (S4)
=
(S4)
Function
These parameters allow you to set up to 15 operating speeds just by switching contact
signals externally. Preset-speed frequencies can be set arbitrarily between the lower limit
frequency
and the upper limit frequency
.
S1
S2
S3
S4