6.25.12 Over-voltage stall protection level
:
Over-voltage stall protection level(high response)
:
Over-voltage stall protection level
*
Refer to 6.13.5 for details.
6.25.13 Under-voltage trip
:
Under-voltage trip mode
:
Under-voltage detection time
=
:
Disabled
・・・・
Inverter stops, but does not trip.(FL is not active)
=
:
Enabled
・・・・
The inverter trips if an under-voltage passes for the time
set with
or over. (FL is active)
Title
Function
Adjustment range
Default setting
Under-voltage trip mode
: Disabled,
: Enabled
Under-voltage detection time
〜
[s]
6.25.14 UV stall level
:
Under-voltage stall level
Title
Function
Adjustment range
Default setting
Under-voltage stall level
〜
[%]
6.25.15 System-supporting sequence (B-timer)
:
System-supporting sequence (B-timer)
Title
Function
Adjustment range
Default setting
System-supporting sequence (B-timer)
: Invalid
〜
[s]
・
Function
This parameter is to select the action when detecting an under-voltage. (Invalid, while the
inverter stops.) If
is set at
(Enabled), it is necessary to set, with
, the time
elapsed before the inverter trips after the detection of an under-voltage.
・
Function
This parameter is used to set the operation level of the regenerative power
ride-through control and the deceleration stop. (Refer to 6.13.2)
・
Function
This parameter is used to set the waiting time for answer from system(Input terminal function
setting: System-supporting sequence (BA:
,
) ). After start of operation, if no answer
is received in set time(
), the inverter trips(
).