E-13
5.5 Factory default setting
:
Standard setting mode selection
Title
Function
Adjustment range
Default setting
Standard setting
mode selection
: -
: 50Hz standard setting
: 60Hz standard setting
: Factory default setting
: Trip clear
: Clearing accumulating operation time
: Initialization of type form information
: Memorization of user-defined parameters
: Reset of user-defined parameters
★
This parameter is used to change the settings of other parameters. Therefore, 0 is always displayed.
★
This parameter cannot be used when the inverter is in operation. So, put the inverter out of operation
before using this parameter.
★
You can check the previous settings by selecting
last set data in status monitor mode. (Refer to 8.1
for details.)
[Set value]
[ 50 Hz standard setting (
=
) ]
Setting
at
causes all the following parameters to be set for operation using a
base frequency of 50Hz.(This does not change the settings of any other parameters.)
・
Maximum frequency
: 50Hz
・
VI/II reference point #2 frequency
: 50Hz
・
Base frequency #1
: 50Hz
・
RR reference point #2 frequency
: 50Hz
・
Base frequency #2
: 50Hz
・
RX reference point #2 frequency
: 50Hz
・
Base frequency #3
: 50Hz
・
RX2 reference point #2 frequency
: 50Hz
・
Base frequency #4
: 50Hz
・
BIN reference point #2 frequency
: 50Hz
・
Upper limit frequency
: 50Hz
・
Pulse reference point #2 frequency
: 50Hz
・
Forward speed limit input level
: 50Hz
・
Point #2 frequency
: 50Hz
・
Reverse speed limit input level
: 50Hz
・
Automatic light-load high-speed operation frequency
: 50Hz
・
Commercial power/inverter switching frequency
: 50Hz
[ 60 Hz standard setting (
=
) ]
Setting
at
causes all the following parameters to be set for operation using a
base frequency of 60Hz.(This does not change the settings of any other parameters.)
・
Maximum frequency
: 60Hz
・
VI/II reference point #2 frequency
: 60Hz
・
Base frequency #1
: 60Hz
・
RR reference point #2 frequency
: 60Hz
・
Base frequency #2
: 60Hz
・
RX reference point #2 frequency
: 60Hz
・
Base frequency #3
: 60Hz
・
RX2 reference point #2 frequency
: 60Hz
・
Base frequency #4
: 60Hz
・
BIN reference point #2 frequency
: 60Hz
・
Upper limit frequency
: 60Hz
・
Pulse reference point #2 frequency
: 60Hz
・
Forward speed limit input level
: 60Hz
・
Point #2 frequency
: 60Hz
・
Reverse speed limit input level
: 60Hz
・
Automatic light-load high-speed operation frequency
: 60Hz
・
Commercial power/inverter switching frequency
: 60Hz
・
Function
This parameter is to set two or more parameters at a time for different commands.
Using this parameter, all parameters can be also return to their respective default settings by
one operation, and save or set specific parameters individually.