C-9
Step 2: Switching from speed control mode to torque control mode, using external
terminals, and assigning the control mode switching
function to the terminal S4.
Control mode
Speed control
Control mode
Torque control
Speed command
RR-CC (Default setting)
Torque command
RX-CC(Default setting)
[Setting procedure: Assigning a control mode switching function to the terminal S4]
Key operated LED display
Operation
The operation frequency is displayed. (Make this setting when
the motor is out of operation.) (If the monitor display mode
setting parameter
is set at
[Running frequency])
Press the [MON] key to call up the first basic parameter
(automatic acceleration/deceleration).
Select
by pressing the
△
or
▽
key.
Pressing the Enter key displays extend parameters starting at
100.
Select
“
”
(input terminal function selection #8 (S4)) by
pressing
△
key.
Press the Enter key to display the parameter setting.
Change the parameter setting to
(control switching) by
pressing
△
key.
Press the Enter key to save the change. Then,
and the
set value are displayed alternately.
MON
▲
ENT
▲ ▼
ENT
▲
ENT
S4: Control mode
switching
CC
CC
RR
S4: Control mode
switching
CC
CC
RX
R/L1
S/L2
T/L3
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
U/T1
V/T2
W/T3
S4-CC connected: Torque control
S4-CC disconnected: Speed control
M
M