F-47
Title
Function
Adjustment range
Default setting
Selection of power running
torque limit #1
: VI(voltage) / II(current)
: RR(volume / voltage)
: RX(voltage)
: RX2(voltage)(optional)
:
Selection of regenerative
torque limit #1
: VI(voltage) / II(current)
: RR(volume / voltage)
: RX(voltage)
: RX2(voltage)(optional)
:
The torque limit function is active in vector control mode. In V/f constant control mode, square reduction
control mode, and automatic torque boost mode, the torque limit function may not be functioned.
In torque control mode, the values set with these parameters limit torque reference.
(2) Positive/negative torque limits
First, you need to set the polarity of each torque limit. Set
at
.
Title
Function
Adjustment range
Setting value
Torque limit
mode (polarity)
: Power running/regenerative torque limit
: Positive/negative torque limit
a) Limiting the torque with parameters
RX-CC
II-CC
100
Motor torque [%]
0
0V
10V
RR-CC
,
VI-CC
Positive
Forward
Negative
Reverse
:
Power running torque limit #1
:
Regenerative torque limit #1
Power running
Regenerative
Power running Regenerative
0V
100
-100
+10V
-10V
0
Motor torque [%]
100
Motor torque [%]
0
4mA
20mA