C-6
3.2.2 Operation from the control panel
[
Control panel operation
]
This section describes how to start/stop the motor, and set the operation frequency with the operating panel.
:
Set the operation freq.
:
Start the motor
:
Stop the motor.
(Deceleration stop)
■
Change the settings of the following two parameters first from the operating panel.
:
(
Control panel: Parameter determining the operation mode
)
:
(
Control panel: Parameter determining the input mode of speed reference
)
[Setting procedure]
Key operated
LED display
Operation
The running frequency is displayed. (Make this setting when the
motor is out of operation.)(If the monitor display mode setting
parameter
is set at
[Running frequency].)
Press the [MON] key to call up the first basic parameter
(automatic acceleration/deceleration).
Select
“
”
by pressing the
△
or
▽
key.
Press the Enter key to display the parameter setting.
(Default setting:
)
Change the parameter setting to
(Operating panel enabled)
by pressing the
△
key.
⇔
Save the change by pressing Enter key. Then,
and the
set value are displayed alternately.
Select
“
”
by pressing
△
key or
▽
key.
Press the Enter key to display the parameter setting.
(Default setting:
).
Change the parameter setting to
(Operating panel input). by
pressing the
△
key.
⇔
Press the Enter key to save the change. Then,
and the
set value are displayed alternately.
*
To return to the standard monitor mode (operation frequency), press MON key.
MON
▲ ▼
ENT
▲ ▼
ENT
▲ ▼
ENT
▲ ▼
ENT
▲
▼
STOP
RUN
★
For coast stop
Change the setting of the parameter
.
★
The operation frequency can be changed
anytime even during operation.)
Motor speed
Coast stop
Motor
IM
G/E
CC RX VI RR PP
F
ST
R
R/L1
U/T1
Control panel
CC
Shipped
with these
terminals
shorted
Ex. of typical connection
S/L2
T/L3
V/T2
W/T3
I I
MCCB
Power
supply