105
8-7-11. Monitor function of remote control switch
When using a remote control with the model name RBC-AMT32UL, the following monitor
functions can be used.
Calling of display screen
<Content>
The sensor temperature or operation status of the remote control, indoor unit, or the outdoor unit can be known by
calling up the service monitor mode from the remote control.
[Procedure]
1
Push
+
buttons simultaneously for 4 seconds or more
to call up the service monitor mode.
The service monitor goes on, and temperature of the CODE No. 00
is firstly displayed.
2
Push the temperature setup
buttons to select the
CODE No. to be monitored.
For displayed codes, refer to the table next page.
3
Push
button to determine the item to be monitored.
Then monitor the sensor temperature or operation status of indoor
unit and the outdoor unit in the corresponding refrigerant line.
4
Pushing
button returns the display to the normal display.