91
8-7-2. Function to start/stop (ON/OFF) indoor unit from outdoor unit
The following functions of the indoor unit can start or stop by the switches on the interface P.C. board of the header unit.
NOTE 1)
This start/stop function only sends the signals from the outdoor unit to the indoor unit, such as start, stop,
operation mode, etc. It does not resend the signals even if the indoor unit does not follow the sent signals.
NOTE 2)
The above controls are not used during abnormal stop.
No
Function
Outline
Setup/Release
7-segment display
1
Cooling test
operation
Changes the mode of all the
connected indoor units collectively
to cooling test operation.
Note)
Control operation same as usual
test operation from remote
control is performed.
[Setup]
Set SW01/SW02/SW03 to [2/5/1], and
press SW04 for 2 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1/1/1].
Section A
[C. ]
Section B
[ – C]
2
Heating test
operation
Changes the mode of all the
connected indoor units collectively
to heating test operation.
Note)
Control operation same as usual
test operation from remote
control is performed.
[Setup]
Set SW01/SW02/SW03 to [2/6/1], and
press SW04 for 2 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1/1/1].
Section A
[H. ]
Section B
[ – H]
3
Batch start
Starts all the connected indoor
units collectively.
Note)
The contents follow to the setup
of remote control.
[Setup]
Set SW01/SW02/SW03 to [2/7/1], and
press SW04 for 2 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1].
Section A
[C.H]
Section B
[ 11]
[ 00] is displayed on Section B for 5
seconds.
Batch stop
Stops all the connected indoor
units collectively.
[Setup]
Set SW01/SW02/SW03 to [2/7/1], and
press SW05 for 2 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1].
Section A
[C.H]
Section B
[ 00]
[ 00] is displayed on Section B for 5
seconds.
4
Individual
start
Starts the specified indoor unit.
Notes)
• The contents follow to the
setup of remote control.
• The other indoor units keep
the status as they are.
[Setup]
Set SW01 to [16], set SW02 and SW03
to address No. (1 to 64) to be started,
and press SW04 for 2 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1/1/1].
Section A
[ ]
Section B
[ ]
Section A: Displays the
corresponding indoor address.
Section B: Displays [ 11] for 5
seconds from operation-ON.
Individual
stop
Stops the specified indoor unit.
Note)
The other indoor units keep the
status as they are.
[Setup]
Set SW01 to [16], set SW02 and SW03
to address No. (1 to 64) to be stopped,
and press SW05 for 2 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1/1/1].
Section A
[ ]
Section B
[ ]
Section A: Displays the
corresponding indoor address.
Section B: Displays [ 00] for 5
seconds from operation-OFF.
Individual
test
operation
Operates the specified indoor unit.
Note)
The other indoor units keep the
status as they are.
[Setup]
Set SW01 to [16], set SW02 and SW03
to address No. to be operated, and
press SW04 for 10 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1/1/1].
Section A
[ ]
Section B
[ ]
Section A: Displays the
corresponding indoor address.
Section B: Displays [ FF] for 5
seconds from test operation-ON.
7-segment display [A]
7-segment display [B]
<Rotary switches>
Содержание MMY-MAP0724HT6UL
Страница 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Страница 230: ...229 MMY MAP0724HT6UL ...
Страница 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Страница 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Страница 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...