20
3
Parts Rating
3-1. Outdoor unit
Name
Model
Specification
MM
Y-MAP0724
∗
MM
Y-MAP0964
∗
MM
Y-MAP1144
∗
1 Compressor
DA421A3FB-29M1
Output: 2.3 kW×2
O
1 Compressor
DA421A3FB-29M1
Output: 2.1 kW×3
O
1 Compressor
DA421A3FB-29M1
Output: 2.1 kW×3
O
2 4-way valve coil
STF
AC208-230 V 60 Hz
O
O
O
3 Pulse motor valve coil
HAM-BD28TF-2
DC12 V
O
O
O
4
2-way valve coil
VPV
AC208-230 V 60 Hz
SV2,SV3A,SV3B,SV3C,SV3D,SV3E
O
AC208-230 V 60 Hz
SV2,SV3A,SV3B,SV3C,SV3D,SV3E,SV3F,SV6
O
O
5
2-way valve coil
FQ-D640
AC208-230 V 60 Hz
SV41,SV42,SV5
O
AC208-230 V 60 Hz
SV41,SV42,SV43
O
O
6 High-pressure SW
ACB-4UB
OFF:3.73 MPa ON:2.9 MPa
O
O
O
7 Pressure sensor (For high pressure) NSK-BC038F-U220
0.5~4.3 V / 0~3.73 MPa
O
O
O
8 Pressure sensor (For low pressure)
NSK-BC010F-U220
0.5~3.5 V / 0~0.98 MPa
O
O
O
9 Fan motor
STF-340A1000-1
DC280 V / 1 kW
O
O
O
10 Case heater (For comp.)
AC240 V / 29 W
O
O
O
11 Case heater (For accum.)
AC240 V / 55 W
O
O
O
12 Fusible plug
73 °C
O
O
O
Содержание MMY-MAP0724HT6UL
Страница 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Страница 230: ...229 MMY MAP0724HT6UL ...
Страница 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Страница 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Страница 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...