170
9-8. Leakage/clogging of refrigerating cycle circuit
List of Check Codes Generated upon Occurrence of Leakage/Clogging in Outdoor Cycle
or Oil Circuit Part
(MMY-MAP0724HT6UL)
Clogging
Leakage
Note:
“XX” represents sub-code
Part
Site of fault
(see next page)
Unit generating
check code
Detected fault and check code
Symptom
Outdoor PMV1, 2
A
Corresponding unit
Activation of high-pressure protection
Activation of low-pressure protection
Discharge temp. error (TD1)
Discharge temp. error (TD2)
P20
H06
P03
P17
Rise of pressure
Fall of pressure
Rise of discharge temp.
(compressor 1)
Rise of discharge temp.
(compressor 2)
Check valve in discharge pipe
convergent section
B
Corresponding unit
High-pressure protection error
High-pressure SW system error
P20
P04-XX
Abnormal rise of pressure
Check valve in discharge pipe
C
Corresponding unit
High-pressure SW system error
P04-XX Abnormal rise of pressure
Check valve in oil-equalization circuit
Capillary
Strainer
D
Corresponding unit
Oil level detection circuit error
Oil level low detection and protection
H16-XX
H07
Oil circuit error or oil level low
SV3A valve
E
Other connected unit Oil level low detection and protection H07
Oil level low
SV3B valve
F
Corresponding unit
Oil level low detection and protection H07
Oil level low
SV3C valve
G
Other connected unit Oil level low detection and protection H07
Oil level low
SV3D valve
SV3D valve circuit capillary
Strainer
H
Corresponding unit
Oil level low detection and protection H07
Oil level low
SV3E valve
I
Corresponding unit
Oil level detection circuit error
Oil level low detection and protection
H16-05
H07
Oil circuit error
Oil level low
Oil level low
Oil return distributor
J
Corresponding unit
Oil level low detection and protection H07
Oil level low
SV3C bypass capillary
K
Corresponding unit
Oil level detection circuit error
H16-04
Oil circuit error
Part
Site of fault
(see next page)
Unit generating
check code
Detected fault and check code
Symptom
Outdoor PMV1, 2
A
Corresponding unit
Outdoor liquid backflow error
Oil level low detection and protection
P13
H07
Refrigerant entrapment
Other connected unit Discharge temp. error (TD1)
Discharge temp. error (TD2)
P03
P17
Rise of discharge temp.
(compressor 1)
Rise of discharge temp.
(compressor 2)
Check valve in discharge pipe
convergent section
B
Corresponding unit
Oil level low detection and protection
Compressor breakdown
Compressor error (lockup)
H07
H01-XX
H02-XX
Refrigerant entrapment
Check valve in discharge pipe
C
Corresponding unit
Oil level low detection and protection
Compressor breakdown
Compressor error (lockup)
H07
H01-XX
H02-XX
Refrigerant entrapment
Check valve in oil-equalization circuit
D
Corresponding unit
Oil level low detection and protection H07
Excessive amount of oil
(Leaking side)
Insufficient amount of oil
(Normal side)
SV3A valve
E
Corresponding unit
Oil level low detection and protection H07
Oil level low
SV3C valve
G
Corresponding unit
Oil level low detection and protection H07
Oil level low
Содержание MMY-MAP0724HT6UL
Страница 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Страница 230: ...229 MMY MAP0724HT6UL ...
Страница 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Страница 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Страница 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Страница 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...